# Termometry

Rodzaje, zasada działania, zastosowania i własny czujnik.

# Termometry: rodzaje, zasada działania i zastosowania

<span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#475569;color:#fff">🎚️ Poziom: podstawy</span><span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#0f766e;color:#fff">🧩 Dotyczy: czujniki temperatury, <abbr title="American Society of Heating, Refrigerating and Air-Conditioning Engineers: amerykańskie stowarzyszenie inżynierów, którego zalecenia opisują temperaturę i wilgotność w serwerowniach">ASHRAE</abbr> TC 9.9 (wydanie 5), <abbr title="International Electrotechnical Commission: międzynarodowa organizacja, która wydaje normy elektrotechniczne, np. IEC 60751 dla czujników Pt100">IEC</abbr> 60751, IEC 60584</span><span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#7c3aed;color:#fff">⏱️ Czas: ~45 min</span>

*Temperatura jest najczęściej mierzoną wielkością w serwerowni, w magazynie i w kuchni, a rodzajów czujników jest kilkanaście. Na tej stronie opisujemy, jak działa każdy z nich, czym się różni od pozostałych i do czego go wybieramy. Wracamy tu, gdy trzeba dobrać czujnik albo zrozumieć, co właściwie pokazuje nam monitoring.*

<details id="bkmrk-%F0%9F%94%A4-skr%C3%B3ty-u%C5%BCyte-na-te"><summary>🔤 Skróty użyte na tej stronie (27)</summary>

<table style="width:100%"><thead><tr><th style="width:18%">Skrót</th><th>Co znaczy</th></tr></thead><tbody><tr><td>**1-Wire**</td><td>Magistrala firmy Dallas, w której czujniki rozmawiają z mikrokontrolerem po jednym przewodzie danych, a każdy czujnik ma własny adres</td></tr><tr><td>**ASHRAE**</td><td>American Society of Heating, Refrigerating and Air-Conditioning Engineers: amerykańskie stowarzyszenie inżynierów, którego zalecenia opisują temperaturę i wilgotność w serwerowniach</td></tr><tr><td>**BMC**</td><td>Baseboard Management Controller: osobny malutki komputer na płycie serwera, który działa nawet przy wyłączonym serwerze i odczytuje m.in. temperatury czujników</td></tr><tr><td>**DIY**</td><td>Do It Yourself: zrób to sam, czyli własnoręcznie zbudowany czujnik zamiast gotowego urządzenia</td></tr><tr><td>**DS18B20**</td><td>Cyfrowy czujnik temperatury z magistralą 1-Wire, z fabrycznym 64-bitowym adresem, popularny w układach domowych i małych serwerowniach</td></tr><tr><td>**DTS**</td><td>Digital Thermal Sensor: wbudowany w procesor cyfrowy czujnik temperatury; w światłowodach to też Distributed Temperature Sensing, czyli pomiar temperatury na całej długości włókna</td></tr><tr><td>**HTTP**</td><td>Hypertext Transfer Protocol: protokół stron WWW</td></tr><tr><td>**I2C**</td><td>Inter-Integrated Circuit: prosta dwuprzewodowa magistrala, którą mały układ (np. czujnik) rozmawia z mikrokontrolerem</td></tr><tr><td>**IEC**</td><td>International Electrotechnical Commission: międzynarodowa organizacja, która wydaje normy elektrotechniczne, np. IEC 60751 dla czujników Pt100</td></tr><tr><td>**IPMI**</td><td>Intelligent Platform Management Interface: standard, przez który administrator pyta kontroler BMC serwera o temperatury, napięcia i obroty wentylatorów</td></tr><tr><td>**ISO**</td><td>International Organization for Standardization: organizacja, która wydaje normy techniczne używane na całym świecie</td></tr><tr><td>**LM35**</td><td>Analogowy scalony czujnik temperatury, który na wyjściu daje 10 mV na każdy stopień Celsjusza</td></tr><tr><td>**NIST**</td><td>National Institute of Standards and Technology: amerykańska agencja standaryzacyjna, tu autor wytycznych SP 800-63B o hasłach</td></tr><tr><td>**NTC**</td><td>Negative Temperature Coefficient: termistor, którego opór maleje, gdy temperatura rośnie</td></tr><tr><td>**PDU**</td><td>Power Distribution Unit: listwa zasilająca w szafie rack, w droższych wersjach z gniazdami mierzonymi i wejściem na czujnik temperatury</td></tr><tr><td>**PKN**</td><td>Polski Komitet Normalizacyjny: instytucja, która wydaje polskie wersje norm i sprzedaje je w katalogu</td></tr><tr><td>**PN-EN**</td><td>Polska Norma będąca wersją normy europejskiej, np. PN-EN 54 dla elementów systemów sygnalizacji pożaru</td></tr><tr><td>**Pt100**</td><td>Platynowy czujnik temperatury o oporze 100 omów w 0 stopni Celsjusza: dokładny i stabilny, stosowany w przemyśle</td></tr><tr><td>**PTC**</td><td>Positive Temperature Coefficient: termistor, którego opór rośnie, gdy temperatura rośnie, często gwałtownie po przekroczeniu progu</td></tr><tr><td>**RTD**</td><td>Resistance Temperature Detector: czujnik z metalowego drutu lub warstwy (np. platyny), którego opór rośnie przewidywalnie z temperaturą</td></tr><tr><td>**SMART**</td><td>Self-Monitoring, Analysis and Reporting Technology: wbudowany w dysk mechanizm zbierający liczniki o jego kondycji, na przykład temperaturę i liczbę realokowanych sektorów, odczytywany programami takimi jak smartctl</td></tr><tr><td>**SMS**</td><td>Short Message Service: krótka wiadomość tekstowa na telefon, która dociera także bez internetu</td></tr><tr><td>**SNMP**</td><td>Simple Network Management Protocol: protokół odczytu stanu urządzeń sieciowych</td></tr><tr><td>**TjMax**</td><td>Junction Temperature Maximum: największa dopuszczalna temperatura rdzenia procesora, od której system zaczyna zwalniać układ</td></tr><tr><td>**TMP117**</td><td>Cyfrowy czujnik temperatury firmy Texas Instruments z magistralą I2C, o dokładności rzędu 0,1 °C</td></tr><tr><td>**TMP36**</td><td>Analogowy scalony czujnik temperatury firmy Analog Devices, który daje napięcie proporcjonalne do temperatury i mierzy także poniżej zera</td></tr><tr><td>**UPS**</td><td>Uninterruptible Power Supply: zasilacz awaryjny, podtrzymuje zasilanie urządzeń na czas zaniku napięcia z sieci</td></tr></tbody></table>

</details>## Z życia wzięte

<div id="bkmrk-%F0%9F%93%96-z-%C5%BBycia-wzi%C4%98tepi%C4%85t" style="border-left:6px solid #b45309;border-radius:10px;padding:14px 18px;margin:18px 0;background:rgba(180,83,9,.07)"><span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#b45309;color:#fff">📖 Z ŻYCIA WZIĘTE</span>

Piątek, 16:05. Pani Halina dzwoni, że Optima na `sql01` ledwo się rusza, a Tomek patrzy na termometr wiszący na ścianie serwerowni w Pamiątkowie: 22 °C, wszystko w normie. Dopiero zapis zdarzeń serwera `hv02` pokazuje temperaturę wlotu 31 °C, bo gorące powietrze z tyłu szafy wraca górą na front i zasila najwyższe serwery. Serwer zwolnił procesor, żeby się nie przegrzać, a razem z nim zwolniły maszyny wirtualne. Ściana mierzyła pokój, a serwer oddycha powietrzem sprzed własnego frontu.

</div>## Skąd się wzięło

<div class="callout info" id="bkmrk-poj%C4%99cie%3A-termoskop.-">**Pojęcie: termoskop.** Przyrząd, który pokazuje, że zrobiło się cieplej albo chłodniej, ale nie ma skali liczbowej. Pierwsze termoskopy działały na rozszerzaniu się powietrza, które wypychało słup wody w rurce.

</div>Galileusz bywa uważany za wynalazcę termoskopu, ale dowody nie są jednoznaczne, a źródła podają daty od około 1593 do 1606 roku \[1\]\[4\]. Za pierwszego, który opisał termoskop na piśmie, uchodzi Santorio Santorio w dziele z 1612 roku, a jego uznaje się też za pierwszego, który dodał skalę i zastosował przyrząd w medycynie \[3\]\[4\]. Ole Rømer dodał skalę do termoskopu w 1701 roku i bywa uznawany za twórcę termometru w dzisiejszym sensie \[1\].

[![Termoskop przypisywany Galileuszowi, eksponat Musée des Arts et Métiers. Taki przyrząd pokazywał tylko, że robi się cieplej albo chłodniej, bez skali liczbowej.](https://commons.wikimedia.org/wiki/Special:FilePath/Mus%C3%A9e_des_Arts_et_M%C3%A9tiers_thermoscope_de_galil%C3%A9e_1592.JPG?width=960)](https://commons.wikimedia.org/wiki/File:Mus%C3%A9e_des_Arts_et_M%C3%A9tiers_thermoscope_de_galil%C3%A9e_1592.JPG)

*📷 Termoskop przypisywany Galileuszowi, eksponat Musée des Arts et Métiers. Taki przyrząd pokazywał tylko, że robi się cieplej albo chłodniej, bez skali liczbowej. Źródło: [Wikimedia Commons](https://commons.wikimedia.org/wiki/File:Mus%C3%A9e_des_Arts_et_M%C3%A9tiers_thermoscope_de_galil%C3%A9e_1592.JPG) (autor i wolna licencja podane na stronie pliku).*

Termometr z kolorowymi kulkami, który nazywamy termometrem Galileusza, nie jest jego dziełem. Zbudowali go uczeni z florenckiej Accademia del Cimento, wśród nich uczeń Galileusza Torricelli, a opis opublikowali w 1666 roku \[2\]. W 1654 roku Ferdynand II Medyceusz zrobił zamknięty termometr alkoholowy z rzetelną skalą, jeden z najwcześniejszych prawdziwych termometrów \[4\].

[![Współczesny termometr z kulkami, zwany termometrem Galileusza, wskazujący na zdjęciu 24 stopnie. Nazwa zostaje z tradycji, bo przyrząd zbudowali uczeni z Accademia del Cimento.](https://commons.wikimedia.org/wiki/Special:FilePath/Galileo_Thermometer_24_degrees.jpg?width=960)](https://commons.wikimedia.org/wiki/File:Galileo_Thermometer_24_degrees.jpg)

*📷 Współczesny termometr z kulkami, zwany termometrem Galileusza, wskazujący na zdjęciu 24 stopnie. Nazwa zostaje z tradycji, bo przyrząd zbudowali uczeni z Accademia del Cimento. Źródło: [Wikimedia Commons](https://commons.wikimedia.org/wiki/File:Galileo_Thermometer_24_degrees.jpg) (autor i wolna licencja podane na stronie pliku).*

Daniel Gabriel Fahrenheit zbudował około 1714 roku rtęciowy termometr i skalę, w której punkt zamarzania wody to 32 stopnie \[3\]\[4\]. Anders Celsius przedstawił w 1742 roku skalę odwróconą: 0 oznaczało wrzenie wody, a 100 jej zamarzanie. Do dzisiejszej postaci skalę obrócono w latach 1743 do 1745, a zasługę przypisuje się Jeanowi-Pierre'owi Christinowi, Carlowi Linnaeusowi i Mårtenowi Strömerowi.

Nazwę „stopień Celsjusza” przyjęto oficjalnie w 1948 roku \[5\]. Skalę absolutną, od zera bezwzględnego, zaproponował William Thomson, późniejszy lord Kelvin, w 1848 roku \[3\].

[![Zabytkowy termometr medyczny z Europy z lat 1851 do 1900. Zastosowanie w medycynie to jedno z najstarszych zastosowań termometru ze skalą.](https://commons.wikimedia.org/wiki/Special:FilePath/Clinical_thermometer,_Europe,_1851-1900_Wellcome_L0058018.jpg?width=960)](https://commons.wikimedia.org/wiki/File:Clinical_thermometer,_Europe,_1851-1900_Wellcome_L0058018.jpg)

*📷 Zabytkowy termometr medyczny z Europy z lat 1851 do 1900. Zastosowanie w medycynie to jedno z najstarszych zastosowań termometru ze skalą. Źródło: [Wikimedia Commons](https://commons.wikimedia.org/wiki/File:Clinical_thermometer,_Europe,_1851-1900_Wellcome_L0058018.jpg) (autor i wolna licencja podane na stronie pliku).*

Elektryczne czujniki zaczęły się od odkrycia z 1821 roku. Thomas Johann Seebeck zauważył, że igła kompasu odchyla się przy obwodzie z dwóch różnych metali, gdy jedno ze złączy jest ogrzane, i nazwał to zjawisko termomagnetycznym. Termin „termoelektryczność” wprowadził dopiero Hans Christian Ørsted \[6\]. W tym samym roku Humphry Davy stwierdził, że oporność metali zależy od temperatury, a w 1871 roku William Siemens zaproponował platynę jako materiał czujnika \[9\]. Hugh Longbourne Callendar zbudował w 1885 roku pierwszy udany komercyjnie platynowy czujnik rezystancyjny, a jego konstrukcja dała początek wzorcowi, który do dziś definiuje międzynarodową skalę temperatury \[9\]\[11\].

Termistory wywodzą się z obserwacji Michaela Faradaya z 1833 roku, który badał siarczek srebra, a komercyjny termistor opracował w latach trzydziestych XX wieku Samuel Ruben \[12\]. Równanie, którym do dziś przeliczamy ich oporność na temperaturę, opublikowali w 1968 roku John Steinhart i Stanley Hart \[13\]. Pomiar bez dotyku ma korzenie w 1800 roku, kiedy William Herschel wykrył promieniowanie podczerwone przez wzrost temperatury na termometrze za czerwonym końcem widma \[25\]. Bolometr, czyli przodek czujnika kamery termowizyjnej, zbudował w 1878 roku Samuel Langley \[24\].

## Rodzaje i zasada działania

<div class="callout info" id="bkmrk-poj%C4%99cie%3A-czujnik-tem">**Pojęcie: czujnik temperatury.** Element, który zamienia temperaturę na coś, co umiemy zmierzyć: długość słupka cieczy, ruch wskazówki, napięcie, oporność albo ilość promieniowania. Termometr to czujnik razem z miejscem, w którym odczytujemy wynik, czyli ze skalą, wyświetlaczem albo przetwornikiem.

</div><div class="callout info" id="bkmrk-poj%C4%99cie%3A-przetwornik">**Pojęcie: przetwornik.** Układ, który odczytuje sygnał z czujnika, na przykład mikrowolty z termopary, i zamienia go na liczbę w stopniach. W czujnikach cyfrowych przetwornik jest zamknięty w tej samej obudowie co element pomiarowy.

</div>Każdy rodzaj poniżej opisujemy tym samym schematem: zasada fizyczna, zakres, dokładność, czas reakcji, zalety, wady i miejsca użycia. Liczby pochodzą z kart katalogowych albo norm i podajemy je z oznaczeniem źródła. Dokładność zawsze dotyczy konkretnego zakresu i warunków, więc nie porównujemy jej mechanicznie między rodzajami.

### Termoskop i termometr cieczowy

<div class="callout info" id="bkmrk-poj%C4%99cie%3A-termometr-c">**Pojęcie: termometr cieczowy.** Szklana rurka (kapilara) ze zbiorniczkiem, w której ciecz rozszerza się razem z temperaturą i wspina po skali. Objętość rtęci rośnie o około 0,018 procent na każdy stopień, a wąska rurka powiększa ten ruch do widocznego \[27\].

</div>Zasada fizyczna to rozszerzalność cieplna cieczy. Rtęć pozwala mierzyć od około -37 do 356 °C \[27\]. Alkohol, zwykle barwiony, jest bezpieczniejszy i mierzy niższe temperatury, ale ma znacznie niższy zakres górny. Trzecim wariantem jest stop galu, indu i cyny, który topi się dopiero w -19 °C i jest dużo mniej toksyczny od rtęci, a nazwa „Galinstan” to znak towarowy firmy Geratherm \[28\]. Taki stop przylega do szkła, więc wymaga innej konstrukcji kapilary niż rtęć \[28\].

- Zakres: rtęć od około -37 do 356 °C, alkohol i stopy galu zależnie od konstrukcji \[27\]\[28\].
- Dokładność: zależy od klasy przyrządu i od odczytu na wysokości oczu, bo błąd paralaksy potrafi dać więcej niż sam przyrząd.
- Czas reakcji: sekundy do minut, zależnie od wielkości zbiorniczka.
- Zalety: nie potrzebuje zasilania, jest prosty i tani, a stary termometr bywa przyzwoitym wzorcem porównawczym.
- Wady: jest kruchy, nie nadaje się do zdalnego odczytu, a rtęć jest trująca.
- Gdzie: termometry okienne i laboratoryjne, wzorce odniesienia. Sprzedaż rtęciowych termometrów konsumenckich w Unii Europejskiej zakończyła się 3 kwietnia 2009 roku \[27\]\[37\].

### Termometr bimetaliczny

<div class="callout info" id="bkmrk-poj%C4%99cie%3A-bimetal.-dw">**Pojęcie: bimetal.** Dwa paski różnych metali o różnej rozszerzalności cieplnej, zgrzane ze sobą na całej długości. Po ogrzaniu metal rozszerzający się mocniej wygina cały pasek, a sam ruch w bok jest znacznie większy niż wydłużenie \[26\].

</div>Pasek zwinięty w spiralę obraca wskazówkę termometru tarczowego, a ten sam ruch zamyka albo otwiera styk w termostacie \[26\]. Wynalazek przypisuje się Johnowi Harrisonowi, który w 1759 roku użył go w chronometrze morskim, żeby wyrównać wpływ temperatury na sprężynę balansu \[26\]. Zakres zależy od pary metali, na przykład stal z miedzią albo inwar z mosiądzem \[26\].

- Zakres: zależny od pary metali, zwykle od kilkudziesięciu stopni poniżej zera do kilkuset powyżej.
- Dokładność: niższa niż w czujnikach elektronicznych, bo mechanika ma tarcie i luz.
- Czas reakcji: sekundy do minut, zależnie od osłony.
- Zalety: nie potrzebuje zasilania, jest odporny i tani.
- Wady: nie da się go wpiąć w monitoring bez dodatkowego czujnika, a odczyt zależy od ustawienia tarczy.
- Gdzie: termometry tarczowe w piekarnikach, grillach i na rurach, termostaty, wyłączniki termiczne \[26\].

### Termopara

<div class="callout info" id="bkmrk-poj%C4%99cie%3A-efekt-seebe">**Pojęcie: efekt Seebecka.** Na styku dwóch różnych metali powstaje napięcie zależne od różnicy temperatur między tym stykiem a drugim końcem obwodu. Zjawisko odkrył w 1821 roku Thomas Johann Seebeck \[6\].

</div><div class="callout info" id="bkmrk-poj%C4%99cie%3A-termopara.-">**Pojęcie: termopara.** Dwa przewody z różnych stopów, zespawane na jednym końcu (złącze pomiarowe). Drugi koniec, czyli zaciski miernika, to złącze zimne, a napięcie zależy od różnicy temperatur między nimi \[7\].

</div><div class="callout info" id="bkmrk-poj%C4%99cie%3A-kompensacja">**Pojęcie: kompensacja zimnego złącza.** Pomiar temperatury zacisków miernika osobnym czujnikiem i dodanie jej do wyniku. Bez niej miernik pokazuje tylko różnicę temperatur, a nie temperaturę złącza \[7\].

</div>[![Rysunek 1. Termopara: napięcie 3,10 mV daje różnicę 75 °C, a dopiero dodanie 25 °C z zacisków daje 100 °C. Tabela pokazuje, że typy różnią się materiałem, czułością i zakresem](https://wiedza.konio-dc.eu/uploads/images/gallery/2026-10/fiz-termometry-termopara.png)](https://wiedza.konio-dc.eu/uploads/images/gallery/2026-10/fiz-termometry-termopara.png)

*🔎 Rysunek 1. Termopara: napięcie 3,10 mV daje różnicę 75 °C, a dopiero dodanie 25 °C z zacisków daje 100 °C. Tabela pokazuje, że typy różnią się materiałem, czułością i zakresem (kliknięcie otwiera pełny rozmiar)*

Najpopularniejszy jest typ K z chromelu i alumelu o czułości około 41 µV/°C, a obok niego typy J (żelazo i konstantan), T (miedź i konstantan) i N (nicrosil i nisil) \[7\]. Typ K mierzy chwilowo od -200 do 1350 °C \[7\]. Norma IEC 60584 dzieli termopary na klasy, a w klasie 2 typu K błąd wynosi ±2,5 °C do około 333 °C, wyżej 0,75 procent wartości, natomiast typ T w klasie 1 osiąga ±0,5 °C w niskich temperaturach \[8\].

[![Termopara typu K, najpopularniejszy rodzaj termopar. Daje napięcie rzędu mikrowoltów na stopień, więc potrzebuje przetwornika.](https://commons.wikimedia.org/wiki/Special:FilePath/Thermocouple_K_%282%29.jpg?width=960)](https://commons.wikimedia.org/wiki/File:Thermocouple_K_%282%29.jpg)

*📷 Termopara typu K, najpopularniejszy rodzaj termopar. Daje napięcie rzędu mikrowoltów na stopień, więc potrzebuje przetwornika. Źródło: [Wikimedia Commons](https://commons.wikimedia.org/wiki/File:Thermocouple_K_%282%29.jpg) (autor i wolna licencja podane na stronie pliku).*

- Zakres: najszerszy ze wszystkich rodzajów, od około -270 do ponad 1300 °C zależnie od typu \[7\].
- Dokładność: zwykle ±1,5 do 2,5 °C, a błąd systemowy poniżej jednego stopnia trudno uzyskać \[7\]\[8\].
- Czas reakcji: bardzo krótki przy cienkiej, odsłoniętej końcówce.
- Zalety: tania, bez zasilania, wytrzymuje bardzo wysokie temperatury \[7\].
- Wady: sygnał to mikrowolty, potrzebna jest kompensacja zimnego złącza i przewody kompensacyjne tego samego typu (KX, JX, TX, NX), a nie zwykła miedź \[45\].
- Gdzie: piece, spaliny, procesy przemysłowe, szybkie termometry sondowe. W serwerowni prawie nigdy.

### Czujnik rezystancyjny RTD, Pt100 i Pt1000

<div class="callout info" id="bkmrk-poj%C4%99cie%3A-rtd.-czujni">**Pojęcie: RTD.** Czujnik, w którym temperaturę odczytujemy z oporności elementu metalowego. Skrót pochodzi od angielskiego resistance temperature detector. Najczęściej element jest z platyny, bo ta zmienia oporność przewidywalnie i powtarzalnie \[9\].

</div><div class="callout info" id="bkmrk-poj%C4%99cie%3A-pt100.-plat">**Pojęcie: Pt100.** Platynowy <abbr title="Resistance Temperature Detector: czujnik z metalowego drutu lub warstwy (np. platyny), którego opór rośnie przewidywalnie z temperaturą">RTD</abbr>, który w 0 °C ma 100 Ω, a Pt1000 ma 1000 Ω. Współczynnik temperaturowy 0,00385 oznacza zmianę o około 0,385 Ω na stopień w <abbr title="Platynowy czujnik temperatury o oporze 100 omów w 0 stopni Celsjusza: dokładny i stabilny, stosowany w przemyśle">Pt100</abbr>, a norma IEC 60751 określa jego tolerancje \[9\]\[10\].

</div><div class="callout info" id="bkmrk-poj%C4%99cie%3A-klasa-dok%C5%82a">**Pojęcie: klasa dokładności.** Dopuszczalny błąd czujnika, który według IEC 60751 rośnie z temperaturą: klasa AA to ±(0,1 + 0,0017·t), A to ±(0,15 + 0,002·t), B to ±(0,3 + 0,005·t), a C to ±(0,6 + 0,01·t), gdzie t to temperatura w stopniach Celsjusza bez znaku \[10\].

</div>[![Rysunek 2. Oporność Pt100 w kilku punktach, klasy dokładności i trzy sposoby podłączenia czujnika. Przy dwóch przewodach opór kabla dodaje się do wyniku, a trzy i cztery przewody to usuwają](https://wiedza.konio-dc.eu/uploads/images/gallery/2026-10/fiz-termometry-rtd-przewody.png)](https://wiedza.konio-dc.eu/uploads/images/gallery/2026-10/fiz-termometry-rtd-przewody.png)

*🔎 Rysunek 2. Oporność Pt100 w kilku punktach, klasy dokładności i trzy sposoby podłączenia czujnika. Przy dwóch przewodach opór kabla dodaje się do wyniku, a trzy i cztery przewody to usuwają (kliknięcie otwiera pełny rozmiar)*

<div class="callout info" id="bkmrk-poj%C4%99cie%3A-uk%C5%82ad-2-%2C-3">**Pojęcie: układ 2-, 3- i 4-przewodowy.** Sposób podłączenia czujnika do miernika. W układzie dwuprzewodowym oporność przewodów dodaje się do oporności czujnika, w trójprzewodowym miernik mierzy ją i odejmuje, a w czteroprzewodowym prąd i napięcie idą osobnymi parami przewodów, więc kabel nie wpływa na wynik \[9\].

</div>Dla przykładu dwa przewody po 0,5 Ω dodają 1 Ω, co daje około 2,6 °C błędu. Klasa B obejmuje od -196 do 600 °C w wersji drutowej i od -50 do 500 °C w wersji cienkowarstwowej, a klasa AA jest dostępna tylko w węższych zakresach \[10\]. Zwykły Pt100 klasy B w 25 °C ma więc tolerancję ±0,43 °C, a klasy A ±0,20 °C.

[![Czujnik Pt100, platynowy czujnik rezystancyjny. Jego oporność zmienia się z temperaturą w przewidywalny sposób, dlatego należy do najdokładniejszych czujników tej strony.](https://commons.wikimedia.org/wiki/Special:FilePath/Pt-100_temperature_sensor.jpg?width=960)](https://commons.wikimedia.org/wiki/File:Pt-100_temperature_sensor.jpg)

*📷 Czujnik Pt100, platynowy czujnik rezystancyjny. Jego oporność zmienia się z temperaturą w przewidywalny sposób, dlatego należy do najdokładniejszych czujników tej strony. Źródło: [Wikimedia Commons](https://commons.wikimedia.org/wiki/File:Pt-100_temperature_sensor.jpg) (autor i wolna licencja podane na stronie pliku).*

- Zakres: od -196 do 600 °C zależnie od wykonania \[10\].
- Dokładność: od ±0,1 do ±0,6 °C w 0 °C zależnie od klasy \[10\].
- Czas reakcji: sekundy, zależnie od osłony.
- Zalety: stabilność w czasie, powtarzalność i wymienność czujników, a platynowy termometr wzorcowy definiuje międzynarodową skalę temperatury \[11\].
- Wady: sygnał jest słaby, potrzebny jest prąd pomiarowy, który lekko nagrzewa element, i kabel trzy- albo czteroprzewodowy.
- Gdzie: przemysł, laboratoria, farmacja, chłodnictwo, rozdzielnie ciepła.

### Termistor NTC i PTC

<div class="callout info" id="bkmrk-poj%C4%99cie%3A-termistor.-">**Pojęcie: termistor.** Rezystor, którego oporność silnie zależy od temperatury. Nazwa to zbitka słów „thermal” i „resistor”, a elementy robi się z prasowanych tlenków metali \[12\].

</div><div class="callout info" id="bkmrk-poj%C4%99cie%3A-ntc-i-ptc.-">**Pojęcie: NTC i PTC.** W termistorze <abbr title="Negative Temperature Coefficient: termistor, którego opór maleje, gdy temperatura rośnie">NTC</abbr> oporność maleje, gdy temperatura rośnie, i takie czujniki najczęściej służą do pomiaru. W termistorze <abbr title="Positive Temperature Coefficient: termistor, którego opór rośnie, gdy temperatura rośnie, często gwałtownie po przekroczeniu progu">PTC</abbr> oporność rośnie z temperaturą, więc używa się go do zabezpieczeń przed przeciążeniem i do samoregulujących grzałek \[12\].

</div>[![Rysunek 3. Krzywa oporności NTC 10 kΩ spada stromo, a Pt100 zmienia się niewiele. Prawy wykres pokazuje, że NTC jest kilkanaście razy czulszy, ale po krzywej, którą trzeba przeliczać](https://wiedza.konio-dc.eu/uploads/images/gallery/2026-10/fiz-termometry-ntc-pt100.png)](https://wiedza.konio-dc.eu/uploads/images/gallery/2026-10/fiz-termometry-ntc-pt100.png)

*🔎 Rysunek 3. Krzywa oporności NTC 10 kΩ spada stromo, a Pt100 zmienia się niewiele. Prawy wykres pokazuje, że NTC jest kilkanaście razy czulszy, ale po krzywej, którą trzeba przeliczać (kliknięcie otwiera pełny rozmiar)*

<div class="callout info" id="bkmrk-poj%C4%99cie%3A-parametr-b.">**Pojęcie: parametr B.** Liczba opisująca, jak stromo spada oporność termistora NTC. Z parametrem B liczymy: `R = R25 · exp(B · (1/T - 1/T25))`, gdzie R25 to oporność w 25 °C, a temperatury podajemy w kelwinach. Dokładniejsze jest równanie Steinharta i Harta: `1/T = A + B·ln(R) + C·(ln R)^3`, którego współczynniki A, B i C podaje producent dla danego termistora \[13\].

</div>Typowy zakres to od -55 do 150 °C, a nowoczesne NTC osiągają ±0,1 do ±0,2 °C w wąskim przedziale \[12\]. Równanie Steinharta i Harta przestaje wystarczać przy pomiarach naukowych, ale do monitoringu wystarcza z zapasem \[13\].

[![Termistor NTC, element, którego oporność spada wraz ze wzrostem temperatury. Dzięki temu mały i tani czujnik wystarcza do monitoringu.](https://commons.wikimedia.org/wiki/Special:FilePath/NTC_Thermistor.jpg?width=960)](https://commons.wikimedia.org/wiki/File:NTC_Thermistor.jpg)

*📷 Termistor NTC, element, którego oporność spada wraz ze wzrostem temperatury. Dzięki temu mały i tani czujnik wystarcza do monitoringu. Źródło: [Wikimedia Commons](https://commons.wikimedia.org/wiki/File:NTC_Thermistor.jpg) (autor i wolna licencja podane na stronie pliku).*

- Zakres: zwykle od -55 do 150 °C \[12\].
- Dokładność: ±0,1 do ±0,2 °C po dobraniu parametrów, w wąskim zakresie \[12\].
- Czas reakcji: bardzo krótki dla małych koralików.
- Zalety: duża czułość, niska cena, mała masa.
- Wady: nieliniowa krzywa, rozrzut między egzemplarzami, samonagrzewanie przy zbyt dużym prądzie.
- Gdzie: zasilacze, baterie, drukarki 3D, urządzenia domowe, motoryzacja \[12\].

### Półprzewodnikowy czujnik scalony

<div class="callout info" id="bkmrk-poj%C4%99cie%3A-czujnik-sca">**Pojęcie: czujnik scalony.** Układ w jednej obudowie, który zawiera element pomiarowy i elektronikę. Producent przeliczył już sygnał z elementu na prosty wynik: napięcie proporcjonalne do temperatury albo liczbę w komunikacie cyfrowym.

</div>Czujniki analogowe są najprostsze. <abbr title="Analogowy scalony czujnik temperatury, który na wyjściu daje 10 mV na każdy stopień Celsjusza">LM35</abbr> daje 10 mV na stopień, mierzy od -55 do 150 °C, a typowy błąd w temperaturze pokojowej to ±0,25 °C \[15\]. <abbr title="Analogowy scalony czujnik temperatury firmy Analog Devices, który daje napięcie proporcjonalne do temperatury i mierzy także poniżej zera">TMP36</abbr> też daje 10 mV na stopień, ale ma przesunięcie 500 mV w 0 °C, czyli 750 mV w 25 °C, mierzy od -40 do 125 °C i pracuje od 2,7 V \[16\].

<div class="callout info" id="bkmrk-poj%C4%99cie%3A-1-wire.-mag">**Pojęcie: 1-Wire.** Magistrala, w której czujnik i procesor łączą się jedną linią danych i masą, a każdy układ ma własny 64-bitowy numer fabryczny, dzięki czemu na jednym przewodzie może pracować wiele czujników.

</div><div class="callout info" id="bkmrk-poj%C4%99cie%3A-i2c.-dwuprz">**Pojęcie: I2C.** Dwuprzewodowa magistrala cyfrowa (zegar i dane), na której procesor rozmawia z czujnikami po adresach.

</div>Cyfrowy <abbr title="Cyfrowy czujnik temperatury z magistralą 1-Wire, z fabrycznym 64-bitowym adresem, popularny w układach domowych i małych serwerowniach">DS18B20</abbr> działa na magistrali <abbr title="Magistrala firmy Dallas, w której czujniki rozmawiają z mikrokontrolerem po jednym przewodzie danych, a każdy czujnik ma własny adres">1-Wire</abbr>, mierzy od -55 do 125 °C, w zakresie od -10 do 85 °C z dokładnością ±0,5 °C, a rozdzielczość można ustawić od 9 do 12 bitów, przy czym pełny pomiar trwa do 750 ms \[14\]. Układ można zasilać z linii danych albo osobnym przewodem od 3,0 do 5,5 V, a po włączeniu jego rejestr zawiera 85 °C \[14\]. <abbr title="Cyfrowy czujnik temperatury firmy Texas Instruments z magistralą I2C, o dokładności rzędu 0,1 °C">TMP117</abbr> działa na <abbr title="Inter-Integrated Circuit: prosta dwuprzewodowa magistrala, którą mały układ (np. czujnik) rozmawia z mikrokontrolerem">I2C</abbr>, ma dokładność ±0,1 °C od -20 do 50 °C, rozdzielczość 0,0078 °C i adres wybieramy spośród czterech, a producent testuje każdy egzemplarz na stanowisku ze wzorcem powiązanym ze wzorcami <abbr title="National Institute of Standards and Technology: amerykańska agencja standaryzacyjna, tu autor wytycznych SP 800-63B o hasłach">NIST</abbr> \[17\].

[![Sonda z cyfrowym czujnikiem DS18B20. To dobry wybór na własne punkty pomiarowe w serwerowni.](https://commons.wikimedia.org/wiki/Special:FilePath/Sensor_DS18B20.jpg?width=960)](https://commons.wikimedia.org/wiki/File:Sensor_DS18B20.jpg)

*📷 Sonda z cyfrowym czujnikiem DS18B20. To dobry wybór na własne punkty pomiarowe w serwerowni. Źródło: [Wikimedia Commons](https://commons.wikimedia.org/wiki/File:Sensor_DS18B20.jpg) (autor i wolna licencja podane na stronie pliku).*

- Zakres: od -55 do 125 lub 150 °C \[14\]\[15\]\[17\].
- Dokładność: od ±0,1 °C (TMP117) przez ±0,5 °C (DS18B20) do ±1 do 2 °C (TMP36) \[14\]\[16\]\[17\].
- Czas reakcji: zależy od obudowy, w sondach metalowych dziesiątki sekund.
- Zalety: gotowy wynik, brak kalibracji, mała cena, łatwe podłączenie do mikrokontrolera.
- Wady: wąski zakres górny, delikatne wyprowadzenia, samonagrzewanie (LM35 około 0,08 °C w spokojnym powietrzu) \[15\].
- Gdzie: płyty główne, monitoring środowiska, własne czujniki <abbr title="Do It Yourself: zrób to sam, czyli własnoręcznie zbudowany czujnik zamiast gotowego urządzenia">DIY</abbr>. W serwerowni to najlepsza klasa do własnych punktów pomiarowych.

### Czujniki w procesorach i dyskach

<div class="callout info" id="bkmrk-poj%C4%99cie%3A-dioda-termi">**Pojęcie: dioda termiczna.** Złącze półprzewodnikowe w układzie scalonym, którego napięcie zależy od temperatury. Procesor ma takich złączy kilka i sam z nich korzysta, żeby zwolnić, zanim się przegrzeje.

</div>W procesorach Intela jest cyfrowy czujnik temperatury, w skrócie <abbr title="Digital Thermal Sensor: wbudowany w procesor cyfrowy czujnik temperatury; w światłowodach to też Distributed Temperature Sensing, czyli pomiar temperatury na całej długości włókna">DTS</abbr>. Sterownik jądra Linuksa `coretemp` odczytuje go dla każdego rdzenia i dla całego układu z rozdzielczością jednego stopnia, a surowy odczyt jest odległością od <abbr title="Junction Temperature Maximum: największa dopuszczalna temperatura rdzenia procesora, od której system zaczyna zwalniać układ">TjMax</abbr>, czyli od maksymalnej temperatury złącza, która zależy od modelu \[18\].

<div class="callout info" id="bkmrk-poj%C4%99cie%3A-smart.-mech">**Pojęcie: SMART.** Mechanizm dysku, który zbiera liczniki o jego kondycji, w tym temperaturę. Atrybut 194 podaje temperaturę w stopniach Celsjusza w najmłodszym bajcie wartości, a atrybut 190 odpowiada 100 minus temperatura \[20\]. Sterownik `drivetemp` udostępnia ten odczyt jądru, a przy zbyt częstym czytaniu na niektórych dyskach może przeszkadzać w usypianiu \[19\].

</div>- Zakres: ograniczony zakresem pracy samego układu.
- Dokładność: rozdzielczość 1 °C, a bezwzględna dokładność zależy od modelu i nie jest gwarantowana \[18\].
- Zalety: są zawsze, nic nie kosztują, widzą temperaturę tam, gdzie zewnętrzny czujnik nigdy nie dotrze.
- Wady: to temperatura złącza albo dysku, nie powietrza, więc nie zastępuje czujnika na wlocie.
- Gdzie: monitoring serwerów, alarmy przegrzania, diagnostyka wentylatorów.

### Pirometr i termometr na podczerwień

<div class="callout info" id="bkmrk-poj%C4%99cie%3A-pirometr.-p">**Pojęcie: pirometr.** Przyrząd mierzący temperaturę bez dotyku, na podstawie promieniowania podczerwonego emitowanego przez powierzchnię. Soczewka skupia promieniowanie na detektorze, a ten zamienia moc promieniowania na sygnał elektryczny \[21\].

</div><div class="callout info" id="bkmrk-poj%C4%99cie%3A-emisyjno%C5%9B%C4%87.">**Pojęcie: emisyjność.** Liczba od 0 do 1 mówiąca, jak skutecznie powierzchnia wysyła promieniowanie w porównaniu z idealnym ciałem. Skóra, woda, beton i czarna farba mają emisyjność powyżej 0,9, a polerowane aluminium około 0,05 \[21\]\[22\].

</div>[![Rysunek 4. Matowa taśma o emisyjności 0,95 pokazuje prawie prawdziwe 80 °C, a polerowane aluminium pokazuje około 29 °C, bo pirometr widzi głównie odbite otoczenie](https://wiedza.konio-dc.eu/uploads/images/gallery/2026-10/fiz-termometry-pirometr-emisyjnosc.png)](https://wiedza.konio-dc.eu/uploads/images/gallery/2026-10/fiz-termometry-pirometr-emisyjnosc.png)

*🔎 Rysunek 4. Matowa taśma o emisyjności 0,95 pokazuje prawie prawdziwe 80 °C, a polerowane aluminium pokazuje około 29 °C, bo pirometr widzi głównie odbite otoczenie (kliknięcie otwiera pełny rozmiar)*

Moc promieniowania rośnie z czwartą potęgą temperatury (prawo Stefana i Boltzmanna), a przyrząd musi wiedzieć, ile promieniowania pochodzi z samej powierzchni, a ile jest odbitym otoczeniem \[21\]. Dlatego błyszczące elementy wyglądają na zimne, a rozwiązaniem jest czarna taśma izolacyjna o emisyjności około 0,97 albo ustawienie emisyjności w przyrządzie \[22\]. Prosty przyrząd ma błąd rzędu ±2 °C, a stosunek odległości do plamki, na przykład 12:1, mówi, jak małą powierzchnię widzi z danej odległości \[21\].

- Zakres: zależy od modelu, od kilkudziesięciu stopni poniżej zera do kilkuset powyżej.
- Dokładność: rzędu ±2 °C w prostych przyrządach i silnie zależna od emisyjności \[21\].
- Czas reakcji: poniżej sekundy.
- Zalety: bez dotyku, szybki, bezpieczny przy elementach pod napięciem, jeśli sprawdzamy z odległości.
- Wady: mierzy tylko powierzchnię, wymaga znajomości emisyjności, szyba i para wodna zakłócają odczyt.
- Gdzie: przeglądy rozdzielnic, silniki, łożyska, kuchnia, termometry czołowe i uszne w medycynie \[21\].

### Kamera termowizyjna

<div class="callout info" id="bkmrk-poj%C4%99cie%3A-mikrobolome">**Pojęcie: mikrobolometr.** Matryca maleńkich elementów, których oporność zmienia się, gdy pochłoną promieniowanie podczerwone o długości fali od 7,5 do 14 µm. Każdy element to jeden piksel obrazu, a matryca nie wymaga chłodzenia \[23\]. Zasadę bolometru wymyślił Samuel Langley w 1878 roku, a materiałem detektora jest najczęściej tlenek wanadu albo krzem amorficzny \[23\]\[24\].

</div><div class="callout info" id="bkmrk-poj%C4%99cie%3A-kamera-term">**Pojęcie: kamera termowizyjna.** Aparat z obiektywem podczerwonym i matrycą mikrobolometrów, który zamienia temperaturę każdego punktu sceny na kolor. Rozdzielczości to zwykle 160×120 albo 320×240, a nowsze modele dochodzą do 640×480 punktów \[23\].

</div>Technologię mikrobolometrów opracował Honeywell w ramach tajnego kontraktu dla armii Stanów Zjednoczonych od końca lat siedemdziesiątych, a odtajniono ją w 1992 roku \[23\]. Kamera widzi tylko powierzchnie i podlega tym samym zasadom emisyjności co pirometr, więc interpretujemy kolory, a nie czytamy ich jak liczb.

[![Ręczna kamera termowizyjna FLIR E8. Pokazuje temperaturę powierzchni jako kolory, więc przy odczycie trzeba pamiętać o emisyjności.](https://commons.wikimedia.org/wiki/Special:FilePath/Flir_E8-Thermal_imaging_camera-Thermographic_camera-01ASD.jpg?width=960)](https://commons.wikimedia.org/wiki/File:Flir_E8-Thermal_imaging_camera-Thermographic_camera-01ASD.jpg)

*📷 Ręczna kamera termowizyjna FLIR E8. Pokazuje temperaturę powierzchni jako kolory, więc przy odczycie trzeba pamiętać o emisyjności. Źródło: [Wikimedia Commons](https://commons.wikimedia.org/wiki/File:Flir_E8-Thermal_imaging_camera-Thermographic_camera-01ASD.jpg) (autor i wolna licencja podane na stronie pliku).*

- Zakres: zależy od modelu, zwykle od kilkudziesięciu stopni poniżej zera do kilkuset powyżej.
- Dokładność: podobnie jak pirometr, zależna od emisyjności, odległości i warunków.
- Czas reakcji: obraz w czasie rzeczywistym.
- Zalety: widzimy rozkład temperatur na całej powierzchni naraz, a nie punkt po punkcie.
- Wady: wysoka cena, szyba blokuje obraz, błyszczące powierzchnie dają błędne wartości.
- Gdzie: rozdzielnice, wycieki i mostki cieplne w budynkach, przegląd szaf, szukanie awarii.

### Czujniki światłowodowe

Światłowód potrafi sam być czujnikiem temperatury. W metodzie rozproszonej (DTS) laser wysyła impuls, a stosunek natężenia dwóch składowych światła rozproszonego Ramana mówi, jaka jest temperatura w danym miejscu włókna. Typowy system ma zasięg ponad 30 km, rozdzielczość przestrzenną około metra i dokładność ±1 °C \[43\]. Druga metoda wykorzystuje siatki Bragga, w których długość fali odbitego światła zmienia się z temperaturą \[44\].

Czujniki światłowodowe są odporne na zakłócenia elektromagnetyczne i bezpieczne w strefach zagrożonych wybuchem \[43\]. Stosuje się je przy kablach energetycznych, w tunelach, rurociągach i do wykrywania pożarów. W typowej serwerowni zwykle ich nie spotykamy, bo trzy czujniki na szafie wystarczą, a koszt jest nieporównywalny.

## Wszystkie rodzaje w jednej tabeli

<table id="bkmrk-rodzajzasadatypowy-z"><thead><tr><th>Rodzaj</th><th>Zasada</th><th>Typowy zakres</th><th>Dokładność (przykład)</th><th>Najlepsze zastosowanie</th></tr></thead><tbody><tr><td>Cieczowy (rtęć, alkohol, stop galu)</td><td>rozszerzalność cieczy</td><td>rtęć od -37 do 356 °C \[27\]</td><td>zależna od klasy i odczytu</td><td>wzorce porównawcze, termometry okienne</td></tr><tr><td>Bimetaliczny</td><td>różna rozszerzalność dwóch metali</td><td>zależny od pary metali \[26\]</td><td>niższa niż elektroniczne</td><td>termometry tarczowe, termostaty</td></tr><tr><td>Termopara</td><td>napięcie Seebecka</td><td>od -200 do 1350 °C (typ K, chwilowo) \[7\]</td><td>±1,5 do 2,5 °C \[8\]</td><td>piece, spaliny, przemysł</td></tr><tr><td>Pt100 i Pt1000</td><td>oporność platyny</td><td>do 600 °C (wersja drutowa) \[10\]</td><td>klasa A ±(0,15 + 0,002·t) \[10\]</td><td>przemysł, laboratoria, farmacja</td></tr><tr><td>Termistor NTC</td><td>oporność półprzewodnika</td><td>od -55 do 150 °C \[12\]</td><td>±0,1 do 0,2 °C w wąskim zakresie \[12\]</td><td>zasilacze, baterie, AGD</td></tr><tr><td>Scalony analogowy</td><td>napięcie proporcjonalne</td><td>LM35 od -55 do 150 °C \[15\]</td><td>LM35 ±0,25 °C typowo \[15\]</td><td>proste układy, dydaktyka</td></tr><tr><td>Scalony cyfrowy</td><td>liczba w komunikacie</td><td>DS18B20 od -55 do 125 °C \[14\]</td><td>±0,5 °C od -10 do 85 °C \[14\]; TMP117 ±0,1 °C \[17\]</td><td>monitoring środowiska, DIY</td></tr><tr><td>Dioda w procesorze, SMART</td><td>napięcie złącza, licznik dysku</td><td>zależny od układu \[18\]\[20\]</td><td>rozdzielczość 1 °C \[18\]</td><td>diagnostyka serwerów</td></tr><tr><td>Pirometr</td><td>promieniowanie podczerwone</td><td>zależny od modelu</td><td>około ±2 °C w prostych \[21\]</td><td>przeglądy, pomiar bez dotyku</td></tr><tr><td>Kamera termowizyjna</td><td>matryca mikrobolometrów</td><td>zależny od modelu</td><td>zależna od emisyjności \[23\]</td><td>rozdzielnice, szafy, budynki</td></tr><tr><td>Światłowodowy</td><td>rozpraszanie światła w włóknie</td><td>zasięg ponad 30 km \[43\]</td><td>±1 °C, rozdzielczość 1 m \[43\]</td><td>kable, tunele, rurociągi</td></tr></tbody></table>

## W serwerowni

### Co zaleca ASHRAE

<div class="callout info" id="bkmrk-poj%C4%99cie%3A-ashrae-tc-9">**Pojęcie: ASHRAE TC 9.9.** Komitet techniczny amerykańskiego stowarzyszenia ASHRAE, który publikuje wytyczne dla centrów danych. W zbiorze „Thermal Guidelines” wyróżnia klasy sprzętu od A1 (najbardziej wymagający, typowe serwery firmowe) do A4 (najbardziej odporny) \[29\].

</div><div class="callout info" id="bkmrk-poj%C4%99cie%3A-temperatura">**Pojęcie: temperatura na wlocie.** Temperatura powietrza, które sprzęt wciąga z przodu szafy. Wytyczne ASHRAE dotyczą właśnie tego miejsca, a nie temperatury pokoju ani powietrza z nawiewu klimatyzacji \[29\]\[30\].

</div><table id="bkmrk-klasazalecany-wlotdo"><thead><tr><th>Klasa</th><th>Zalecany wlot</th><th>Dopuszczalny wlot</th><th>Maksymalny punkt rosy</th></tr></thead><tbody><tr><td>A1</td><td>od 18 do 27 °C</td><td>od 15 do 32 °C</td><td>17 °C</td></tr><tr><td>A2</td><td>od 18 do 27 °C</td><td>od 10 do 35 °C</td><td>21 °C</td></tr><tr><td>A3</td><td>od 18 do 27 °C</td><td>od 5 do 40 °C</td><td>24 °C</td></tr><tr><td>A4</td><td>od 18 do 27 °C</td><td>od 5 do 45 °C</td><td>24 °C</td></tr></tbody></table>

Źródłem tabeli jest piąte wydanie wytycznych (2021, poprawione 2024) \[29\]. Zalecany zakres jest jednakowy dla wszystkich klas, a klasy różnią się tylko zakresem dopuszczalnym \[29\]. W Zielonej zakładamy ostrożnie klasę A1, dopóki karta katalogowa danego serwera nie wskazuje wprost innej klasy.

<div class="callout info" id="bkmrk-poj%C4%99cie%3A-punkt-rosy.">**Pojęcie: punkt rosy.** Temperatura, w której para wodna z powietrza zaczyna się skraplać. Im wyższy punkt rosy, tym wilgotniejsze powietrze, a na zimnych elementach może wtedy osiadać woda.

</div>W klasie A1 dopuszczalna wilgotność mieści się między punktem rosy -12 °C i 8 procent wilgotności względnej a punktem rosy 17 °C i 80 procent wilgotności względnej \[29\]. Przyjmujemy z tego dwa progi dla Zabbixa: ostrzeżenie powyżej 27 °C, czyli górna granica zalecana, i alarm krytyczny powyżej 32 °C, czyli górna granica dopuszczalna klasy A1.

### Gdzie mierzyć

<div class="callout info" id="bkmrk-poj%C4%99cie%3A-zimny-i-gor">**Pojęcie: zimny i gorący korytarz.** Układ szaf, w którym fronty dwóch rzędów patrzą na siebie w jednym korytarzu, a klimatyzacja nawiewa tam chłodne powietrze. Serwery wciągają je z przodu, a ogrzane wypuszczają z tyłu do osobnego, gorącego korytarza.

</div>ASHRAE opisuje dwa podejścia. Do stałego nadzoru stawia się czujnik co czwarta szafa, na wysokości około 1,5 m, w osi zimnego korytarza, a do sprawdzenia instalacji mierzy się środek wlotu najwyższego, środkowego i najniższego serwera w szafie, około 5 cm przed obudową \[31\]. Pierwsza metoda jest łatwa, ale potrafi przegapić gorące powietrze wracające górą nad szafą, a druga pokazuje to, co serwer naprawdę zasysa \[31\].

[![Rysunek 5. Plan serwerowni z zimnym i gorącym korytarzem oraz przekrój szafy z trzema czujnikami na wlocie. Czujnik u góry pokazuje 31 °C, choć termometr na ścianie wskazuje 22 °C](https://wiedza.konio-dc.eu/uploads/images/gallery/2026-10/fiz-termometry-serwerownia-wlot.png)](https://wiedza.konio-dc.eu/uploads/images/gallery/2026-10/fiz-termometry-serwerownia-wlot.png)

*🔎 Rysunek 5. Plan serwerowni z zimnym i gorącym korytarzem oraz przekrój szafy z trzema czujnikami na wlocie. Czujnik u góry pokazuje 31 °C, choć termometr na ścianie wskazuje 22 °C (kliknięcie otwiera pełny rozmiar)*

Zalecamy więc po trzy stałe czujniki na wlocie w szafach z największą gęstością sprzętu (góra, środek, dół) oraz jeden w gorącym korytarzu, który nie służy do alarmów, tylko do oceny różnicy temperatur. Jak taki zestaw zbudować i podłączyć do Zabbixa, opisuje strona [Termometry w praktyce: wybór, montaż i własny czujnik (DIY)](https://wiedza.konio-dc.eu/books/warstwa-fizyczna/page/termometry-w-praktyce-wybor-montaz-i-wlasny-czujnik-diy).

### Dlaczego temperatura pokoju to nie to samo co wlot serwera

Powietrze w serwerowni nie jest jednorodne. Jeśli chłodne i gorące powietrze się mieszają, temperatura przy wlocie może być o 15 °C i więcej wyższa od temperatury na nawiewie \[30\]. Powodami są recyrkulacja nad szafą, przecieki przez puste miejsca w szafie bez zaślepek i słabe odseparowanie korytarzy.

Dlatego czujnik na ścianie albo przy klimatyzacji nie mówi nic o tym, co dostaje serwer. Z drugiej strony czujnik za szafą mierzy tylko wylot, który z natury jest cieplejszy.

### Czujniki, które już mamy

<div class="callout info" id="bkmrk-poj%C4%99cie%3A-bmc-i-ipmi.">**Pojęcie: BMC i IPMI.** <abbr title="Baseboard Management Controller: osobny malutki komputer na płycie serwera, który działa nawet przy wyłączonym serwerze i odczytuje m.in. temperatury czujników">BMC</abbr> to osobny, mały komputer wbudowany w płytę serwera, który działa nawet wyłączony system. <abbr title="Intelligent Platform Management Interface: standard, przez który administrator pyta kontroler BMC serwera o temperatury, napięcia i obroty wentylatorów">IPMI</abbr> to standard rozmowy z nim po sieci, dzięki któremu odczytujemy czujniki bez udziału systemu operacyjnego \[32\].

</div>Serwery firmowe mają zwykle czujnik wlotu, czujnik wylotu i temperatury podzespołów. Zabbix odczytuje je elementem typu IPMI agent, a serwer Zabbixa musi mieć uruchomione procesy pobierające dane IPMI (parametr `StartIPMIPollers`) \[32\].

Przykład odczytu z BMC serwera `hv02` programem `ipmitool` z komendą `sdr type temperature`:

```text
Inlet Temp       | 04h | ok  |  7.1 | 31 degrees C
Exhaust Temp     | 01h | ok  |  7.1 | 44 degrees C
Temp             | 0Eh | ok  |  3.1 | 52 degrees C
```

Dla dysków korzystamy z mechanizmu <abbr title="Self-Monitoring, Analysis and Reporting Technology: wbudowany w dysk mechanizm zbierający liczniki o jego kondycji, na przykład temperaturę i liczbę realokowanych sektorów, odczytywany programami takimi jak smartctl">SMART</abbr>. Przykład wiersza z wyniku `smartctl -A` dla dysku w `bkp01`:

```text
194 Temperature_Celsius     0x0022   064   045   000    Old_age   Always       -       36 (Min/Max 21/55)
```

Zasilacze awaryjne (<abbr title="Uninterruptible Power Supply: zasilacz awaryjny, podtrzymuje zasilanie urządzeń na czas zaniku napięcia z sieci">UPS</abbr>) mają czujnik temperatury baterii, który przez <abbr title="Simple Network Management Protocol: protokół odczytu stanu urządzeń sieciowych">SNMP</abbr> udostępnia obiekt `upsBatteryTemperature` o numerze `1.3.6.1.2.1.33.1.2.7`, czyli temperaturę otoczenia przy obudowie baterii w stopniach Celsjusza \[33\]. Inteligentne listwy zasilające (<abbr title="Power Distribution Unit: listwa zasilająca w szafie rack, w droższych wersjach z gniazdami mierzonymi i wejściem na czujnik temperatury">PDU</abbr>) często mają złącze na zewnętrzną sondę temperatury i wilgotności, a odczyt również idzie przez SNMP.

<div class="callout info" id="bkmrk-poj%C4%99cie%3A-pdu.-listwa">**Pojęcie: PDU.** Listwa zasilająca montowana w szafie, która rozdziela prąd na serwery. Wersje inteligentne mierzą pobór prądu, a niektóre mają wejścia na zewnętrzne czujniki środowiska.

</div>### Termowizja przy przeglądzie rozdzielnicy

Kamera termowizyjna pozwala zobaczyć miejsca, w których połączenie elektryczne grzeje się bardziej niż sąsiednie, zanim dojdzie do awarii. Porównujemy zaciski tej samej fazy i trzy fazy między sobą, bo jednakowo obciążone punkty powinny mieć zbliżoną temperaturę. Prace przy rozdzielnicy pod napięciem wykonują tylko osoby z uprawnieniami, a zasady opisuje książka [Uprawnienia SEP](https://wiedza.konio-dc.eu/books/uprawnienia-sep/page/uprawnienia-sep-dlaczego-informatyk-potrzebuje-papieru-elektryka).

Odczyt błyszczących zacisków wymaga ostrożności, bo niska emisyjność zaniża wynik (Rysunek 4). Podejrzany punkt sprawdzamy drugi raz po przyklejeniu czarnej taśmy albo pirometrem w wersji z regulowaną emisyjnością.

### Gotowe urządzenia komercyjne

Nie wskazujemy producentów, tylko klasy urządzeń, które spotykamy w serwerowniach.

- Sieciowy czujnik środowiska do szafy z wejściami na sondy temperatury i wilgotności, odczytywany przez SNMP albo <abbr title="Hypertext Transfer Protocol: protokół stron WWW">HTTP</abbr>.
- Sondy podłączane do inteligentnej listwy PDU albo do karty sieciowej UPS.
- Rejestrator temperatury z certyfikatem wzorcowania, z alarmem <abbr title="Short Message Service: krótka wiadomość tekstowa na telefon, która dociera także bez internetu">SMS</abbr> albo pocztą, do chłodni i mroźni.
- Bezprzewodowe czujniki z komunikacją radiową dalekiego zasięgu, na baterię, do magazynu.
- Ręczna kamera termowizyjna do przeglądów rozdzielnic.
- Wzorcowy termometr kontaktowy z certyfikatem, do sprawdzania pozostałych.

### Poza serwerownią

Chłodnia i magazyn Zielonej w Swarzędzu to łańcuch chłodniczy żywności. Marek kieruje magazynem, w którym towar schłodzony i mrożony nie może się ogrzać na żadnym etapie od przyjęcia do wydania. Dyrektywa Komisji 92/2/EWG mówi, że głęboko mrożona żywność ma być w temperaturze -18 °C albo niższej, a termometry kontrolne mają mieć dokładność ±0,5 °C w zakresie od -20 do 30 °C, rozdzielczość 0,1 °C i ważne świadectwo wzorcowania \[34\]. W komorach chłodniczych temperaturę sprawdza się przy drzwiach, w środku i przy powrocie powietrza \[34\].

Rozporządzenie Komisji (WE) nr 37/2005 wymaga rejestratorów temperatury w środkach transportu i magazynach żywności głęboko mrożonej, zgodnych z normami EN 12830, EN 13485 i EN 13486, a zapisy przechowuje się co najmniej rok \[35\]. Norma EN 12830 obejmuje systemy rejestracji od -80 do 85 °C dla żywności, leków i produktów krwiopochodnych \[36\]. Z tego powodu własny czujnik DIY nie zastępuje w chłodni certyfikowanego rejestratora.

W medycynie termometr szklany z rtęcią zastąpiono elektronicznymi, a gotowe czujniki scalone, jak TMP117, są projektowane pod normę <abbr title="International Organization for Standardization: organizacja, która wydaje normy techniczne używane na całym świecie">ISO</abbr> 80601-2-56 dla termometrów medycznych \[17\]. Termometry czołowe i uszne korzystają z zasady pirometru \[21\]. W kuchni spotykamy termometry tarczowe na bimetalu oraz cyfrowe sondy z termistorem albo termoparą, które wbijamy w środek produktu. W domu to samo robi termostat grzejnika z bimetalem albo czujnikiem NTC \[12\]\[26\].

## Mity i sprostowania

<table id="bkmrk-obiegowa-wersjajak-j"><thead><tr><th>Obiegowa wersja</th><th>Jak jest naprawdę</th></tr></thead><tbody><tr><td>Termometr wymyślił Galileusz.</td><td>Galileusz najpewniej zbudował termoskop bez skali, a skalę dodał Santorio w 1612 roku. Termometr z kulkami nazywany jego imieniem zbudowano we Florencji i opisano w 1666 roku \[1\]\[2\]\[4\].</td></tr><tr><td>Celsjusz od początku miał 0 przy zamarzaniu wody.</td><td>W 1742 roku miał 0 przy wrzeniu i 100 przy zamarzaniu. Odwrócono to w latach 1743 do 1745, a o zasługę spierają się Christin, Linnaeus i Strömer \[5\].</td></tr><tr><td>Pt100 pokazuje 100 stopni.</td><td>Liczba mówi o oporności w 0 °C, czyli 100 omów. Temperaturę liczymy z tablic normy \[9\].</td></tr><tr><td>Termopara mierzy temperaturę złącza i tyle.</td><td>Mierzy różnicę względem zacisków miernika, więc bez kompensacji zimnego złącza wynik jest zaniżony o temperaturę zacisków \[7\].</td></tr><tr><td>DS18B20 pokazał 85 stopni, więc jest gorąco.</td><td>85 °C to wartość, z jaką startuje rejestr czujnika po włączeniu, zanim policzy pierwszy pomiar \[14\].</td></tr><tr><td>W serwerowni jest 22 °C, więc serwery też mają 22 °C.</td><td>Serwer ma temperaturę powietrza ze swojego wlotu, która potrafi być o kilkanaście stopni wyższa od temperatury pokoju \[30\]\[31\].</td></tr><tr><td>Im chłodniej w serwerowni, tym lepiej.</td><td>Zalecany wlot to od 18 do 27 °C. Schłodzenie poniżej kosztuje energię i nie jest potrzebne \[29\].</td></tr><tr><td>Kamera termowizyjna pokazuje prawdziwą temperaturę każdej rzeczy.</td><td>Błyszczące powierzchnie o niskiej emisyjności wyglądają na zimniejsze, niż są \[21\]\[22\].</td></tr></tbody></table>

## Oś czasu

<table id="bkmrk-datawydarzenieoko%C5%82o-"><thead><tr><th>Data</th><th>Wydarzenie</th></tr></thead><tbody><tr><td>około 1593 do 1606</td><td>Galileusz buduje termoskop, daty w źródłach różnią się, a autorstwo bywa kwestionowane \[1\]\[4\]</td></tr><tr><td>1612</td><td>Santorio Santorio opisuje termoskop i dodaje skalę \[3\]\[4\]</td></tr><tr><td>1654</td><td>Ferdynand II Medyceusz buduje zamknięty termometr alkoholowy ze skalą \[4\]</td></tr><tr><td>1666</td><td>Accademia del Cimento publikuje opis termometru z kulkami \[2\]</td></tr><tr><td>1701</td><td>Ole Rømer dodaje skalę do termoskopu \[1\]</td></tr><tr><td>około 1714</td><td>Fahrenheit buduje termometr rtęciowy i skalę \[3\]\[4\]</td></tr><tr><td>1742</td><td>Celsius przedstawia skalę, w której 0 to wrzenie, a 100 zamarzanie \[5\]</td></tr><tr><td>1743 do 1745</td><td>skala Celsjusza zostaje odwrócona \[5\]</td></tr><tr><td>1759</td><td>Harrison stosuje bimetal w chronometrze morskim \[26\]</td></tr><tr><td>1800</td><td>Herschel odkrywa promieniowanie podczerwone \[25\]</td></tr><tr><td>1821</td><td>Seebeck opisuje zjawisko termoelektryczne, Davy stwierdza zależność oporności od temperatury \[6\]\[9\]</td></tr><tr><td>1833</td><td>Faraday obserwuje ujemny współczynnik temperaturowy siarczku srebra \[12\]</td></tr><tr><td>1848</td><td>William Thomson proponuje skalę absolutną \[3\]</td></tr><tr><td>1871</td><td>Siemens proponuje platynę na czujnik rezystancyjny \[9\]</td></tr><tr><td>1878</td><td>Langley wynajduje bolometr \[24\]</td></tr><tr><td>1883</td><td>Wróblewski i Olszewski w Krakowie skraplają tlen \[38\]\[39\]</td></tr><tr><td>1885</td><td>Callendar buduje pierwszy komercyjny platynowy czujnik rezystancyjny \[9\]</td></tr><tr><td>lata trzydzieste XX wieku</td><td>Samuel Ruben opracowuje komercyjny termistor \[12\]</td></tr><tr><td>1968</td><td>Steinhart i Hart publikują równanie dla termistorów \[13\]</td></tr><tr><td>od końca lat siedemdziesiątych</td><td>Honeywell rozwija mikrobolometry, odtajnione w 1992 roku \[23\]</td></tr><tr><td>1995</td><td>specyfikacja SMART trafia do domeny publicznej \[20\]</td></tr><tr><td>3 kwietnia 2009</td><td>w Unii Europejskiej kończy się sprzedaż konsumencka termometrów rtęciowych \[27\]\[37\]</td></tr><tr><td>2021</td><td>piąte wydanie wytycznych ASHRAE Thermal Guidelines \[29\]</td></tr></tbody></table>

## Wątek polski

W kwietniu 1883 roku w Krakowie Zygmunt Wróblewski i Karol Olszewski jako pierwsi na świecie skroplili tlen, azot i tlenek węgla w stanie trwałym \[38\]\[39\]. W 1884 roku Olszewski skroplił wodór i osiągnął rekordową wtedy temperaturę -225 °C \[38\]. Źródła, które sprawdziliśmy, nie podają, jakich termometrów używali, więc tego nie opisujemy.

Polska norma na termoelementy to <abbr title="Polska Norma będąca wersją normy europejskiej, np. PN-EN 54 dla elementów systemów sygnalizacji pożaru">PN-EN</abbr> 60584-1 \[42\]. Dla czujników Pt100 międzynarodowa norma IEC 60751 jest stosowana w Polsce na co dzień, ale numeru i roku aktualnego wydania w katalogu <abbr title="Polski Komitet Normalizacyjny: instytucja, która wydaje polskie wersje norm i sprzedaje je w katalogu">PKN</abbr> nie sprawdziliśmy, więc go nie podajemy. Rejestratory w chłodnictwie żywności podlegają unijnej normie EN 12830, o której pisze rozporządzenie 37/2005 \[35\]\[36\].

Czujniki temperatury produkują w Polsce między innymi Lumel z Zielonej Góry, który ma w ofercie czujniki, przetworniki i rejestratory oraz laboratorium badawczo-wzorcujące \[40\], oraz CZAKI Thermo-Product z Raszyna, działający od 1978 roku \[41\]. Nie udało się nam potwierdzić, czy i w jakim zakresie Główny Urząd Miar realizuje skalę temperatury, dlatego odsyłamy do jego wykazu usług metrologicznych. Polskiego wynalazcy termometru nie znaleźliśmy w sprawdzonych źródłach i nie twierdzimy, że taki istniał.

## Częste błędy

<table id="bkmrk-objawprzyczynaco-rob"><thead><tr><th>Objaw</th><th>Przyczyna</th><th>Co robimy</th></tr></thead><tbody><tr><td>Pokój 22 °C, a serwer zgłasza przegrzanie</td><td>czujnik na ścianie zamiast na wlocie</td><td>dokładamy czujniki na wlocie szafy, na trzech wysokościach</td></tr><tr><td>Termopara pokazuje temperaturę zaniżoną o kilkanaście stopni</td><td>brak kompensacji zimnego złącza albo zwykły miedziany przewód zamiast kompensacyjnego</td><td>używamy miernika z kompensacją i przewodu tego samego typu co termopara \[7\]\[45\]</td></tr><tr><td>Pt100 na długim kablu pokazuje o 2 do 3 °C za dużo</td><td>układ dwuprzewodowy</td><td>przechodzimy na trzy albo cztery przewody</td></tr><tr><td>Po wymianie termistora wynik skoczył</td><td>inny parametr B albo rozrzut egzemplarzy</td><td>wpisujemy parametry konkretnego typu z karty katalogowej i sprawdzamy w punkcie 0 °C \[12\]\[13\]</td></tr><tr><td>DS18B20 pokazuje 85 °C po restarcie</td><td>wartość startowa rejestru albo spadek zasilania</td><td>odrzucamy odczyt 85,0 i sprawdzamy zasilanie i rezystor podciągający \[14\]</td></tr><tr><td>Termowizja pokazuje zimny zacisk w gorącej rozdzielnicy</td><td>niska emisyjność powierzchni</td><td>naklejamy czarną taśmę albo ustawiamy emisyjność \[22\]</td></tr><tr><td>W Zabbixie brak danych z czujnika</td><td>rozłączony kabel albo wyłączona płytka</td><td>wyzwalacz braku danych, a potem sprawdzenie zasilania i połączeń</td></tr></tbody></table>

## 🎯 Ćwiczenia

1. Dlaczego odczyt 22 °C z termometru na ścianie serwerowni nie wystarcza do oceny temperatury serwerów?

<details id="bkmrk-odpowied%C5%BA-serwer-ch%C5%82"><summary>Odpowiedź</summary>

Serwer chłodzi się powietrzem z własnego wlotu z przodu szafy, a ta temperatura zależy od mieszania się gorącego i zimnego powietrza. Może być o kilkanaście stopni wyższa od temperatury pokoju, zwłaszcza u góry szafy \[30\]\[31\]. Dlatego mierzymy na wlocie, na trzech wysokościach.

</details>1. Termopara typu K daje 3,10 mV, a zaciski miernika mają 25 °C. Jaka jest temperatura złącza pomiarowego, jeśli czułość to około 41 µV/°C?

<details id="bkmrk-odpowied%C5%BA-3%2C10-mv-dz"><summary>Odpowiedź</summary>

3,10 mV dzielone przez 0,041 mV/°C daje około 75 °C różnicy. Po dodaniu 25 °C zacisków wychodzi około 100 °C. Miernik bez kompensacji pokazałby 75 °C \[7\].

</details>1. Pt100 w układzie dwuprzewodowym podłączono kablem, w którym każdy przewód ma 0,4 Ω. Ile stopni błędu to daje?

<details id="bkmrk-odpowied%C5%BA-dwa-przewo"><summary>Odpowiedź</summary>

Dwa przewody dodają 0,8 Ω. Zmiana o 1 °C to około 0,385 Ω, więc błąd wynosi około 2,1 °C. W układzie trójprzewodowym miernik odjąłby tę stratę \[9\].

</details>1. DS18B20 po włączeniu zasilania pokazuje dokładnie 85,0 °C. Co o tym sądzimy i co robimy w skrypcie?

<details id="bkmrk-odpowied%C5%BA-85-%C2%B0c-to-w"><summary>Odpowiedź</summary>

85 °C to wartość początkowa rejestru czujnika, zanim wykona pierwszy pomiar, a nie temperatura powietrza \[14\]. W skrypcie odrzucamy ten odczyt i czekamy na następny. Jeśli wraca stale, sprawdzamy zasilanie i rezystor podciągający.

</details>1. Pirometr pokazuje 30 °C na błyszczącym zacisku, a po przyklejeniu czarnej taśmy 62 °C. Który wynik uznajemy za wiarygodny i dlaczego?

<details id="bkmrk-odpowied%C5%BA-62-%C2%B0c%2C-bo-"><summary>Odpowiedź</summary>

62 °C, bo taśma ma emisyjność około 0,97, więc pirometr widzi własne promieniowanie powierzchni. Polerowany metal ma emisyjność bliską 0,05 i odbija otoczenie, więc pokazuje wartość zbliżoną do temperatury pokoju \[21\]\[22\].

</details>**Źródła:**

1. [Wikipedia, Thermoscope](https://en.wikipedia.org/wiki/Thermoscope)
2. [Wikipedia, Galileo thermometer](https://en.wikipedia.org/wiki/Galileo_thermometer)
3. [World History Encyclopedia, The Thermometer and the Scientific Revolution](https://www.worldhistory.org/article/2275/the-thermometer--the-scientific-revolution)
4. [Brannan, History of Thermometers](https://www.brannan.co.uk/knowledge_base/history-of-thermometers/)
5. [Wikipedia, Celsius](https://en.wikipedia.org/wiki/Celsius)
6. [Wikipedia, Thermoelectric effect](https://en.wikipedia.org/wiki/Thermoelectric_effect)
7. [Wikipedia, Thermocouple](https://en.wikipedia.org/wiki/Thermocouple)
8. [TC Direct, Thermocouple accuracies (IEC 60584-1)](https://tcdirect.co.uk/thermocouple-sensors/thermocouple-accuracies.aspx)
9. [Wikipedia, Resistance thermometer](https://en.wikipedia.org/wiki/Resistance_thermometer)
10. [WIKA, Pt100 in class B or F 0.3, what does IEC 60751 say](https://blog.wika.com/en/knowhow/pt100-in-class-b-oder-f-03-what-does-iec-60751-say/)
11. [Chemistry World, Callendar's platinum thermometer](https://chemistryworld.com/opinion/callendars-platinum-thermometer/4015866.article)
12. [Wikipedia, Thermistor](https://en.wikipedia.org/wiki/Thermistor)
13. [Wikipedia, Steinhart-Hart equation](https://en.wikipedia.org/wiki/Steinhart%E2%80%93Hart_equation)
14. [Analog Devices, karta katalogowa DS18B20](https://www.analog.com/media/en/technical-documentation/data-sheets/DS18B20.pdf)
15. [Texas Instruments, karta katalogowa LM35](https://www.ti.com/lit/ds/symlink/lm35.pdf)
16. [Analog Devices, karta katalogowa TMP35, TMP36, TMP37](https://www.analog.com/media/en/technical-documentation/data-sheets/TMP35_36_37.pdf)
17. [Texas Instruments, karta katalogowa TMP117](https://www.ti.com/lit/ds/symlink/tmp117.pdf)
18. [Dokumentacja jądra Linuksa, coretemp](https://docs.kernel.org/hwmon/coretemp.html)
19. [Dokumentacja jądra Linuksa, drivetemp](https://www.kernel.org/doc/html/latest/hwmon/drivetemp.html)
20. [Wikipedia, S.M.A.R.T.](https://en.wikipedia.org/wiki/Self-Monitoring,_Analysis_and_Reporting_Technology)
21. [Wikipedia, Infrared thermometer](https://en.wikipedia.org/wiki/Infrared_thermometer)
22. [ThermoWorks, Emissivity Table](https://blog.thermoworks.com/emissivity/)
23. [Wikipedia, Microbolometer](https://en.wikipedia.org/wiki/Microbolometer)
24. [Wikipedia, Bolometer](https://en.wikipedia.org/wiki/Bolometer)
25. [Wikipedia, Infrared](https://en.wikipedia.org/wiki/Infrared)
26. [Wikipedia, Bimetallic strip](https://en.wikipedia.org/wiki/Bimetallic_strip)
27. [Wikipedia, Mercury-in-glass thermometer](https://en.wikipedia.org/wiki/Mercury_thermometer)
28. [Wikipedia, Galinstan](https://en.wikipedia.org/wiki/Galinstan)
29. [ASHRAE, Thermal Guidelines, 5th edition, karta referencyjna](https://www.ashrae.org/file%20library/technical%20resources/bookstore/supplemental%20files/therm-gdlns-5th-r-e-refcard.pdf)
30. [Upsite, What is the difference between ASHRAE's recommended and allowable limits, part 4](https://www.upsite.com/blog/what-is-the-difference-between-ashraes-recommended-and-allowable-data-center-environmental-limits-part-4/)
31. [Upsite, Data Center Temperature Sensor Location](https://www.upsite.com/blog/data-center-temperature-sensor-location/)
32. [Zabbix 7.0, IPMI checks](https://www.zabbix.com/documentation/7.0/en/manual/config/items/itemtypes/ipmi)
33. [Observium, UPS-MIB (RFC 1628), upsBatteryTemperature](https://mibs.observium.org/mib/UPS-MIB)
34. [Dyrektywa Komisji 92/2/EWG](https://eur-lex.europa.eu/eli/dir/1992/2/oj)
35. [Rozporządzenie Komisji (WE) nr 37/2005](https://www.legislation.gov.uk/eur/2005/37/data.html)
36. [EVS, EN 12830:2018](https://www.evs.ee/en/evs-en-12830-2018)
37. [RMF24, Termometry rtęciowe odchodzą do lamusa](https://www.rmf24.pl/fakty/news-termometry-rteciowe-odchodza-do-lamusa,nId,69177)
38. [Wikipedia, Karol Olszewski](https://en.wikipedia.org/wiki/Karol_Olszewski)
39. [Uniwersytet Jagielloński, 130. rocznica skroplenia gazów trwałych w Krakowie](https://fais.uj.edu.pl/documents/41628/4279661/Folder%20130%20rocznicy%20skroplenia%20gaz%C3%B3w%20trwa%C5%82ych%20w%20Krakowie.pdf)
40. [Lumel S.A.](https://www.lumel.com.pl/)
41. [CZAKI Thermo-Product](https://www.czaki.pl/)
42. [Wikipedia (pl), Termopara](https://pl.wikipedia.org/wiki/Termopara)
43. [Wikipedia, Distributed temperature sensing](https://en.wikipedia.org/wiki/Distributed_temperature_sensing)
44. [Wikipedia, Fiber Bragg grating](https://en.wikipedia.org/wiki/Fiber_Bragg_grating)
45. [Thermosense Direct, Thermocouple technical reference](https://www.thermosensedirect.com/media/thermoattachment/products/attachments/thermocouple_technical_reference.pdf)

# Termometry w praktyce: wybór, montaż i własny czujnik (DIY)

<span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#475569;color:#fff">🎚️ Poziom: średnio</span><span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#0f766e;color:#fff">🧩 Dotyczy: <abbr title="Tani mikrokontroler z Wi-Fi i Bluetooth firmy Espressif: malutki komputer, z którego budujemy własne czujniki sieciowe">ESP32</abbr>, <abbr title="Oprogramowanie, które zamienia ESP32 w gotowy czujnik sieciowy bez pisania kodu od zera, a odczyty udostępnia przez sieć">ESPHome</abbr> 2026.x, <abbr title="Cyfrowy czujnik temperatury z magistralą 1-Wire, z fabrycznym 64-bitowym adresem, popularny w układach domowych i małych serwerowniach">DS18B20</abbr>, Raspberry Pi <abbr title="Operating System: system operacyjny">OS</abbr>, Zabbix 7.0 <abbr title="Long Term Support: wersja z długim wsparciem poprawkami">LTS</abbr></span><span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#7c3aed;color:#fff">⏱️ Czas: ~90 min</span>

*Budujemy własny zestaw czujników temperatury do szafy serwerowej: ESP32 z czterema sondami DS18B20 na jednej magistrali i alarmami w Zabbixie na `mon01`, a krócej wariant na Raspberry Pi. Wracamy tu przy montażu nowego zestawu, wymianie sondy i szukaniu przyczyny braku danych. Komendy ESPHome wykonujemy na stacji administratora z Pythonem 3.12 albo nowszym i dostępem do sieci serwerowni, a komendy drugiego wariantu na samej malince jako użytkownik z uprawnieniami sudo.*

<details id="bkmrk-%F0%9F%94%A4-skr%C3%B3ty-u%C5%BCyte-na-te"><summary>🔤 Skróty użyte na tej stronie (24)</summary>

<table style="width:100%"><thead><tr><th style="width:18%">Skrót</th><th>Co znaczy</th></tr></thead><tbody><tr><td>**1-Wire**</td><td>Magistrala firmy Dallas, w której czujniki rozmawiają z mikrokontrolerem po jednym przewodzie danych, a każdy czujnik ma własny adres</td></tr><tr><td>**API**</td><td>Application Programming Interface: sposób, w jaki programy rozmawiają ze sobą</td></tr><tr><td>**ASHRAE**</td><td>American Society of Heating, Refrigerating and Air-Conditioning Engineers: amerykańskie stowarzyszenie inżynierów, którego zalecenia opisują temperaturę i wilgotność w serwerowniach</td></tr><tr><td>**CE**</td><td>Community Edition: darmowa, społecznościowa wersja Dockera, w odróżnieniu od płatnej wersji Enterprise</td></tr><tr><td>**DIY**</td><td>Do It Yourself: zrób to sam, czyli własnoręcznie zbudowany czujnik zamiast gotowego urządzenia</td></tr><tr><td>**DS18B20**</td><td>Cyfrowy czujnik temperatury z magistralą 1-Wire, z fabrycznym 64-bitowym adresem, popularny w układach domowych i małych serwerowniach</td></tr><tr><td>**ESP32**</td><td>Tani mikrokontroler z Wi-Fi i Bluetooth firmy Espressif: malutki komputer, z którego budujemy własne czujniki sieciowe</td></tr><tr><td>**ESPHome**</td><td>Oprogramowanie, które zamienia ESP32 w gotowy czujnik sieciowy bez pisania kodu od zera, a odczyty udostępnia przez sieć</td></tr><tr><td>**GPIO**</td><td>General Purpose Input Output: uniwersalny pin mikrokontrolera, który można ustawić jako wejście albo wyjście</td></tr><tr><td>**HTTP**</td><td>Hypertext Transfer Protocol: protokół stron WWW</td></tr><tr><td>**IT**</td><td>Information Technology: dział albo praca związana z komputerami i infrastrukturą firmy</td></tr><tr><td>**JSON**</td><td>JavaScript Object Notation: tekstowy format danych z klamrami i cudzysłowami</td></tr><tr><td>**JSONPath**</td><td>Zapis ścieżki, która wskazuje jedną wartość w dokumencie JSON, np. $.value to pole value na samym wierzchu</td></tr><tr><td>**LTS**</td><td>Long Term Support: wersja z długim wsparciem poprawkami</td></tr><tr><td>**MQTT**</td><td>Message Queuing Telemetry Transport: lekki protokół, w którym urządzenia wysyłają krótkie wiadomości na nazwane tematy przez serwer pośredniczący</td></tr><tr><td>**OS**</td><td>Operating System: system operacyjny</td></tr><tr><td>**PoE**</td><td>Power over Ethernet: zasilanie urządzenia tym samym kablem sieciowym, którym płyną dane</td></tr><tr><td>**ppoż.**</td><td>Przeciwpożarowy: dotyczący ochrony przed pożarem, na przykład centrala ppoż.</td></tr><tr><td>**REST**</td><td>sposób budowania API przez zwykłe żądania HTTP (GET, POST) zamiast osobnego protokołu</td></tr><tr><td>**SMS**</td><td>Short Message Service: krótka wiadomość tekstowa na telefon, która dociera także bez internetu</td></tr><tr><td>**URL**</td><td>Uniform Resource Locator: adres strony lub zasobu</td></tr><tr><td>**USB**</td><td>Universal Serial Bus: standard portów i urządzeń podłączanych do komputera, tu pendrive'y i inne nośniki wymienne</td></tr><tr><td>**Wi-Fi**</td><td>Sieć bezprzewodowa: wygodna w biurze, ale w serwerowni dokłada kolejną możliwą przyczynę awarii</td></tr><tr><td>**YAML**</td><td>YAML Ain't Markup Language: format plików konfiguracyjnych oparty na wcięciach</td></tr></tbody></table>

</details>## Fiszka

<div id="bkmrk-%F0%9F%9F%A0-zmienia-system-ins" style="border:1px solid rgba(217,119,6,.35);border-left:6px solid #d97706;border-radius:10px;padding:12px 18px 6px 18px;margin:20px 0;background:rgba(217,119,6,.06)"><span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#d97706;color:#fff">🟠 ZMIENIA SYSTEM</span>

### Instalacja ESPHome: pipx install esphome

```bash
pipx install esphome
```

ESPHome to narzędzie, które z jednego pliku <abbr title="YAML Ain't Markup Language: format plików konfiguracyjnych oparty na wcięciach">YAML</abbr> buduje program dla płytki ESP32 i wgrywa go przez <abbr title="Universal Serial Bus: standard portów i urządzeń podłączanych do komputera, tu pendrive'y i inne nośniki wymienne">USB</abbr> albo przez sieć. Wersja 2026.9.1 wymaga Pythona 3.12 albo nowszego \[1\].

Przykład:

```text
  installed package esphome 2026.9.1, installed using Python 3.13.5
  These apps are now globally available
    - esphome
done!
```

🔤 **ESPHome** = Oprogramowanie, które zamienia ESP32 w gotowy czujnik sieciowy bez pisania kodu od zera, a odczyty udostępnia przez sieć · **YAML** = YAML Ain't Markup Language: format plików konfiguracyjnych oparty na wcięciach · **ESP32** = Tani mikrokontroler z Wi-Fi i Bluetooth firmy Espressif: malutki komputer, z którego budujemy własne czujniki sieciowe · **USB** = Universal Serial Bus: standard portów i urządzeń podłączanych do komputera, tu pendrive'y i inne nośniki wymienne · **pipx** = instaluje narzedzia napisane w Pythonie, kazde we wlasnym, odizolowanym srodowisku, bez mieszania zaleznosci miedzy programami

</div><div id="bkmrk-%F0%9F%9F%A2-tylko-odczyt-wygen" style="border:1px solid rgba(22,163,74,.35);border-left:6px solid #16a34a;border-radius:10px;padding:12px 18px 6px 18px;margin:20px 0;background:rgba(22,163,74,.06)"><span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#16a34a;color:#fff">🟢 TYLKO ODCZYT</span>

### Wygenerowanie klucza API: openssl rand -base64 32

```bash
openssl rand -base64 32
```

Klucz szyfrujący natywne <abbr title="Application Programming Interface: sposób, w jaki programy rozmawiają ze sobą">API</abbr> ESPHome to 32 losowe bajty zapisane w base64. Wynik wpisujemy w sekcji `api` pliku konfiguracyjnego \[2\].

<p class="callout success">W serwerowni Zielonej płytki to `esp01` i `esp02`: ESP32 z Ethernetem i zasilaniem <abbr title="Power over Ethernet: zasilanie urządzenia tym samym kablem sieciowym, którym płyną dane">PoE</abbr>, a nie z <abbr title="Sieć bezprzewodowa: wygodna w biurze, ale w serwerowni dokłada kolejną możliwą przyczynę awarii">Wi-Fi</abbr>. Kabel nie zależy od zasięgu w szafie, a PoE zasila płytkę z przełącznika, więc nie ma osobnego zasilacza. Plik poniżej opisuje płytkę `esp02` w wariancie z Wi-Fi, który zostaje dla domu i do prób na biurku. W serwerowni zamiast bloku `wifi` wpisujemy blok `ethernet` jak na stronie [ESPHome i urządzenia: adopcja esp01 i esp02, API albo MQTT, nazwy encji](https://wiedza.konio-dc.eu/books/home-assistant/page/esphome-i-urzadzenia-adopcja-esp01-i-esp02-api-albo-mqtt-nazwy-encji), a w sekcji `esp32` ustawiamy `board: esp32-poe`:</p>

```yaml
ethernet:
  type: LAN8720
  mdc_pin: GPIO23
  mdio_pin: GPIO18
  clk:
    pin: GPIO17
    mode: CLK_OUT
  phy_addr: 0
  power_pin: GPIO12
  manual_ip:
    static_ip: 10.20.10.71
    gateway: 10.20.10.1
    subnet: 255.255.255.0
    dns1: 10.20.10.11
```

Blok pochodzi z przykładu w dokumentacji ESPHome dla płytki Olimex ESP32-POE, a numery pinów sprawdzamy w opisie własnej płytki. Ethernet zajmuje część pinów, więc inne magistrale ustawiamy na wolnych. Magistrala <abbr title="Magistrala firmy Dallas, w której czujniki rozmawiają z mikrokontrolerem po jednym przewodzie danych, a każdy czujnik ma własny adres">1-Wire</abbr> na GPIO4 z pliku poniżej mieści się bez zmian.

🔤 **API** = Application Programming Interface: sposób, w jaki programy rozmawiają ze sobą · **ESPHome** = Oprogramowanie, które zamienia ESP32 w gotowy czujnik sieciowy bez pisania kodu od zera, a odczyty udostępnia przez sieć · **ESP32** = Tani mikrokontroler z Wi-Fi i Bluetooth firmy Espressif: malutki komputer, z którego budujemy własne czujniki sieciowe · **PoE** = Power over Ethernet: zasilanie urządzenia tym samym kablem sieciowym, którym płyną dane · **Wi-Fi** = Sieć bezprzewodowa: wygodna w biurze, ale w serwerowni dokłada kolejną możliwą przyczynę awarii · **MQTT** = Message Queuing Telemetry Transport: lekki protokół, w którym urządzenia wysyłają krótkie wiadomości na nazwane tematy przez serwer pośredniczący · **1-Wire** = Magistrala firmy Dallas, w której czujniki rozmawiają z mikrokontrolerem po jednym przewodzie danych, a każdy czujnik ma własny adres · **openssl** = zestaw narzędzi do certyfikatów i szyfrowania

</div><div id="bkmrk-%F0%9F%94%B5-plik-konfiguracyjn" style="border:1px solid rgba(37,99,235,.35);border-left:6px solid #2563eb;border-radius:10px;padding:12px 18px 6px 18px;margin:20px 0;background:rgba(37,99,235,.06)"><span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#2563eb;color:#fff">🔵 PLIK KONFIGURACYJNY</span>

### Plik konfiguracyjny ESPHome: esp02.yaml

```yaml
esphome:
  name: esp02
  friendly_name: esp02

esp32:
  board: esp32dev
  framework:
    type: esp-idf

logger:

wifi:
  ssid: "NazwaSieciWifi"
  password: "HasloSieciWifi"
  ap:
    ssid: "esp02"
    password: "HasloAwaryjne"

# Bez klienta API (Home Assistant) płytka restartowałaby się co 15 minut,
# a u nas dane pobiera Zabbix przez web_server, więc wyłączamy ten restart.
api:
  encryption:
    # Przykładowy klucz (32 bajty w base64). Własny generujemy poleceniem openssl rand -base64 32.
    key: "0690dTduZJXaRAhYiVWcgHzWAV4sXEigdsftww8qW+4="
  reboot_timeout: 0s

ota:
  - platform: esphome
    password: "HasloOta"

web_server:
  port: 80
  auth:
    username: "nazwa_usera"
    password: "HasloWebServera"

one_wire:
  - platform: gpio
    pin: GPIO4

sensor:
  # Adresy poniżej są przykładowe: podmieniamy je na adresy z dziennika (patrz niżej).
  - platform: dallas_temp
    name: "wlot_dol"
    address: 0x8c0000046e9b4f28
    resolution: 12
    update_interval: 30s
    filters:
      - offset: 0.0
  - platform: dallas_temp
    name: "wlot_srodek"
    address: 0x3d0000046e9c1a28
    resolution: 12
    update_interval: 30s
    filters:
      - offset: 0.0
  - platform: dallas_temp
    name: "wlot_gora"
    address: 0xe20000046e9d7b28
    resolution: 12
    update_interval: 30s
    filters:
      - offset: 0.0
  - platform: dallas_temp
    name: "korytarz_goracy"
    address: 0x510000046e9e2c28
    resolution: 12
    update_interval: 30s
    filters:
      - offset: 0.0
  - platform: wifi_signal
    name: "wifi_sygnal"
    update_interval: 60s
```

Plik opisuje całą płytkę: sieć Wi-Fi, szyfrowane API, aktualizacje przez sieć, serwer <abbr title="Hypertext Transfer Protocol: protokół stron WWW">HTTP</abbr> z prostym interfejsem <abbr title="sposób budowania API przez zwykłe żądania HTTP (GET, POST) zamiast osobnego protokołu">REST</abbr>, magistralę 1-Wire na pinie GPIO4 i cztery czujniki. Składnia `one_wire` z `platform: gpio` oraz `dallas_temp` jest aktualna w dokumentacji ESPHome \[3\]\[4\]. Nazwy czujników celowo nie mają spacji ani polskich liter, bo wchodzą do adresu <abbr title="Uniform Resource Locator: adres strony lub zasobu">URL</abbr>.

W prawdziwym pliku hasła trzymamy w `secrets.yaml` i zapisujemy je jako `!secret nazwa`. Tutaj stoją placeholdery, żeby plik był jednym blokiem do skopiowania.

Przykład wpisów w pliku `secrets.yaml` i odwołań do nich:

```text
# secrets.yaml
wifi_haslo: "HasloSieciWifi"
api_klucz: "0690dTduZJXaRAhYiVWcgHzWAV4sXEigdsftww8qW+4="   # przykład, własny klucz generujemy poleceniem openssl rand -base64 32
ota_haslo: "HasloOta"

# w esp02.yaml
wifi:
  password: !secret wifi_haslo
api:
  encryption:
    key: !secret api_klucz
ota:
  - platform: esphome
    password: !secret ota_haslo
```

🔤 **ESPHome** = Oprogramowanie, które zamienia ESP32 w gotowy czujnik sieciowy bez pisania kodu od zera, a odczyty udostępnia przez sieć · **Wi-Fi** = Sieć bezprzewodowa: wygodna w biurze, ale w serwerowni dokłada kolejną możliwą przyczynę awarii · **API** = Application Programming Interface: sposób, w jaki programy rozmawiają ze sobą · **HTTP** = Hypertext Transfer Protocol: protokół stron WWW · **REST** = sposób budowania API przez zwykłe żądania HTTP (GET, POST) zamiast osobnego protokołu · **1-Wire** = Magistrala firmy Dallas, w której czujniki rozmawiają z mikrokontrolerem po jednym przewodzie danych, a każdy czujnik ma własny adres · **URL** = Uniform Resource Locator: adres strony lub zasobu

</div><div id="bkmrk-%F0%9F%94%B5-plik-konfiguracyjn-1" style="border:1px solid rgba(37,99,235,.35);border-left:6px solid #2563eb;border-radius:10px;padding:12px 18px 6px 18px;margin:20px 0;background:rgba(37,99,235,.06)"><span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#2563eb;color:#fff">🔵 PLIK KONFIGURACYJNY</span>

### Zamiana API na MQTT: sekcja mqtt

```yaml
mqtt:
  broker: "NazwaBrokeraMqtt"
  username: "nazwa_usera"
  password: "HasloMqtt"
  topic_prefix: "serwerownia/esp02"
```

Ten blok wpisujemy w miejsce sekcji `api`, jeśli dane mają iść przez brokera <abbr title="Message Queuing Telemetry Transport: lekki protokół, w którym urządzenia wysyłają krótkie wiadomości na nazwane tematy przez serwer pośredniczący">MQTT</abbr>, a nie przez Home Assistanta. Jeśli zostawimy oba, a nie ma klienta API, trzeba ustawić `reboot_timeout: 0s` w sekcji `api` \[5\].

🔤 **API** = Application Programming Interface: sposób, w jaki programy rozmawiają ze sobą · **MQTT** = Message Queuing Telemetry Transport: lekki protokół, w którym urządzenia wysyłają krótkie wiadomości na nazwane tematy przez serwer pośredniczący

</div><div id="bkmrk-%F0%9F%9F%A2-tylko-odczyt-spraw" style="border:1px solid rgba(22,163,74,.35);border-left:6px solid #16a34a;border-radius:10px;padding:12px 18px 6px 18px;margin:20px 0;background:rgba(22,163,74,.06)"><span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#16a34a;color:#fff">🟢 TYLKO ODCZYT</span>

### Sprawdzenie pliku: esphome config esp02.yaml

```bash
esphome config esp02.yaml
```

Polecenie wczytuje plik, sprawdza składnię i parametry i wypisuje je w pełnej postaci, niczego nie wgrywając. Kończy się komunikatem `Configuration is valid!`.

🔤 **esphome** = ESPHome: buduje i wgrywa oprogramowanie na ESP32 z pliku YAML, pokazuje logi urządzenia

</div><div id="bkmrk-%F0%9F%9F%A2-tylko-odczyt-wgran" style="border:1px solid rgba(22,163,74,.35);border-left:6px solid #16a34a;border-radius:10px;padding:12px 18px 6px 18px;margin:20px 0;background:rgba(22,163,74,.06)"><span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#16a34a;color:#fff">🟢 TYLKO ODCZYT</span>

### Wgranie programu przez USB: esphome run esp02.yaml

```bash
esphome run esp02.yaml
```

Przy pierwszym wgraniu płytkę podłączamy kablem USB do stacji administratora. Kolejne aktualizacje idą przez sieć, według ustawień z sekcji `ota`.

🔤 **USB** = Universal Serial Bus: standard portów i urządzeń podłączanych do komputera, tu pendrive'y i inne nośniki wymienne · **esphome** = ESPHome: buduje i wgrywa oprogramowanie na ESP32 z pliku YAML, pokazuje logi urządzenia

</div><div id="bkmrk-%F0%9F%9F%A2-tylko-odczyt-odczy" style="border:1px solid rgba(22,163,74,.35);border-left:6px solid #16a34a;border-radius:10px;padding:12px 18px 6px 18px;margin:20px 0;background:rgba(22,163,74,.06)"><span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#16a34a;color:#fff">🟢 TYLKO ODCZYT</span>

### Odczyt adresów czujników: esphome logs esp02.yaml

```bash
esphome logs esp02.yaml
```

Po starcie ESPHome skanuje magistralę i wypisuje w dzienniku adresy wszystkich znalezionych urządzeń, nawet jeśli żaden czujnik nie jest jeszcze opisany w pliku \[3\]. Skanowanie widać także wtedy, gdy plik ma tylko sekcję `one_wire`.

Przykład (skrócony, bez znaczników czasu i nazw modułów):

```text
  Found devices:
    0x8c0000046e9b4f28 (DS18B20)
    0x3d0000046e9c1a28 (DS18B20)
    0xe20000046e9d7b28 (DS18B20)
    0x510000046e9e2c28 (DS18B20)
```

🔤 **ESPHome** = Oprogramowanie, które zamienia ESP32 w gotowy czujnik sieciowy bez pisania kodu od zera, a odczyty udostępnia przez sieć · **esphome** = ESPHome: buduje i wgrywa oprogramowanie na ESP32 z pliku YAML, pokazuje logi urządzenia

</div><div id="bkmrk-%F0%9F%9F%A2-tylko-odczyt-odczy-1" style="border:1px solid rgba(22,163,74,.35);border-left:6px solid #16a34a;border-radius:10px;padding:12px 18px 6px 18px;margin:20px 0;background:rgba(22,163,74,.06)"><span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#16a34a;color:#fff">🟢 TYLKO ODCZYT</span>

### Odczyt czujnika przez REST: curl

```bash
curl --user nazwa_usera http://NazwaCzujnika/sensor/wlot_gora
```

Przy takim zapisie `curl` pyta o hasło, więc nie zostaje ono w historii poleceń. Serwer HTTP płytki odpowiada obiektem <abbr title="JavaScript Object Notation: tekstowy format danych z klamrami i cudzysłowami">JSON</abbr> z polem `value`, które Zabbix wyciąga w następnym kroku \[6\].

Przykład:

```text
{"id":"sensor/wlot_gora","state":"26.1 °C","value":26.1}
```

🔤 **REST** = sposób budowania API przez zwykłe żądania HTTP (GET, POST) zamiast osobnego protokołu · **HTTP** = Hypertext Transfer Protocol: protokół stron WWW · **JSON** = JavaScript Object Notation: tekstowy format danych z klamrami i cudzysłowami · **curl** = client URL: pobieranie i wysyłanie przez HTTP z terminala

</div><div id="bkmrk-%F0%9F%9F%A2-tylko-odczyt-edycj" style="border:1px solid rgba(22,163,74,.35);border-left:6px solid #16a34a;border-radius:10px;padding:12px 18px 6px 18px;margin:20px 0;background:rgba(22,163,74,.06)"><span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#16a34a;color:#fff">🟢 TYLKO ODCZYT</span>

### Edycja pliku konfiguracyjnego Raspberry Pi: sudoedit /boot/firmware/config.txt

```bash
sudoedit /boot/firmware/config.txt
```

Na Raspberry Pi OS plik `config.txt` leży w partycji startowej pod `/boot/firmware/` \[7\]. Na końcu pliku dopisujemy linię z następnej fiszki.

🔤 **OS** = Operating System: system operacyjny · **sudoedit** = sudo edit: bezpieczne otwarcie pliku z uprawnieniami administratora we własnym edytorze, z zapisem pliku dopiero po wyjściu

</div><div id="bkmrk-%F0%9F%94%B5-plik-konfiguracyjn-2" style="border:1px solid rgba(37,99,235,.35);border-left:6px solid #2563eb;border-radius:10px;padding:12px 18px 6px 18px;margin:20px 0;background:rgba(37,99,235,.06)"><span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#2563eb;color:#fff">🔵 PLIK KONFIGURACYJNY</span>

### Włączenie magistrali 1-Wire: dtoverlay=w1-gpio

```ini
dtoverlay=w1-gpio
```

Nakładka `w1-gpio` uruchamia sterownik 1-Wire na pinie GPIO4, a pin można zmienić parametrem `gpiopin` \[8\]. Zmiana wchodzi w życie po ponownym uruchomieniu.

🔤 **1-Wire** = Magistrala firmy Dallas, w której czujniki rozmawiają z mikrokontrolerem po jednym przewodzie danych, a każdy czujnik ma własny adres

</div><div id="bkmrk-%F0%9F%9F%A2-tylko-odczyt-ponow" style="border:1px solid rgba(22,163,74,.35);border-left:6px solid #16a34a;border-radius:10px;padding:12px 18px 6px 18px;margin:20px 0;background:rgba(22,163,74,.06)"><span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#16a34a;color:#fff">🟢 TYLKO ODCZYT</span>

### Ponowne uruchomienie systemu: sudo reboot

```bash
sudo reboot
```

🔤 **reboot** = restart systemu: zamyka usługi i uruchamia komputer od nowa

</div><div id="bkmrk-%F0%9F%9F%A2-tylko-odczyt-lista" style="border:1px solid rgba(22,163,74,.35);border-left:6px solid #16a34a;border-radius:10px;padding:12px 18px 6px 18px;margin:20px 0;background:rgba(22,163,74,.06)"><span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#16a34a;color:#fff">🟢 TYLKO ODCZYT</span>

### Lista czujników 1-Wire: ls /sys/bus/w1/devices/

```bash
ls /sys/bus/w1/devices/
```

Każdy czujnik DS18B20 ma katalog zaczynający się od `28-`, a dalej jego numer fabryczny. Prefiks `28` to kod rodziny układu \[9\].

Przykład:

```text
28-3c01d6075a21  28-3c01d6075b32  28-3c01d6075c43  w1_bus_master1
```

🔤 **1-Wire** = Magistrala firmy Dallas, w której czujniki rozmawiają z mikrokontrolerem po jednym przewodzie danych, a każdy czujnik ma własny adres · **DS18B20** = Cyfrowy czujnik temperatury z magistralą 1-Wire, z fabrycznym 64-bitowym adresem, popularny w układach domowych i małych serwerowniach · **ls** = list: wypisz zawartość katalogu

</div><div id="bkmrk-%F0%9F%9F%A2-tylko-odczyt-odczy-2" style="border:1px solid rgba(22,163,74,.35);border-left:6px solid #16a34a;border-radius:10px;padding:12px 18px 6px 18px;margin:20px 0;background:rgba(22,163,74,.06)"><span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#16a34a;color:#fff">🟢 TYLKO ODCZYT</span>

### Odczyt jednego czujnika: cat w1\_slave

```bash
cat /sys/bus/w1/devices/28-NumerCzujnika/w1_slave
```

(gdzie `28-NumerCzujnika` to nazwa katalogu czujnika z poprzedniej fiszki)

Plik ma dwie linie. Pierwsza kończy się słowem `YES`, gdy suma kontrolna się zgadza, a druga zawiera temperaturę w tysięcznych stopnia po `t=`.

Przykład:

```text
4b 01 4b 46 7f ff 05 10 d8 : crc=d8 YES
4b 01 4b 46 7f ff 05 10 d8 t=20687
```

🔤 **cat** = concatenate: sklej i wypisz pliki

</div><div id="bkmrk-%F0%9F%9F%A0-zmienia-system-ins-1" style="border:1px solid rgba(217,119,6,.35);border-left:6px solid #d97706;border-radius:10px;padding:12px 18px 6px 18px;margin:20px 0;background:rgba(217,119,6,.06)"><span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#d97706;color:#fff">🟠 ZMIENIA SYSTEM</span>

### Instalacja programu zabbix\_sender: sudo apt install zabbix-sender

```bash
sudo apt install zabbix-sender
```

`zabbix_sender` to mały program, który wysyła pojedyncze wartości do serwera Zabbix, bez agenta na maszynie \[10\].

🔤 **apt** = Advanced Package Tool: menedżer pakietów Debiana i Ubuntu

</div><div id="bkmrk-%F0%9F%9F%A2-tylko-odczyt-wysy%C5%82" style="border:1px solid rgba(22,163,74,.35);border-left:6px solid #16a34a;border-radius:10px;padding:12px 18px 6px 18px;margin:20px 0;background:rgba(22,163,74,.06)"><span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#16a34a;color:#fff">🟢 TYLKO ODCZYT</span>

### Wysyłka testowa wartości: zabbix\_sender

```bash
zabbix_sender -z NazwaSerweraZabbix -s NazwaHosta -k KluczElementu -o Wartosc -vv
```

(gdzie `NazwaHosta` to nazwa hosta dokładnie taka, jak w Zabbixie, z rozróżnieniem wielkości liter, a `KluczElementu` to klucz elementu typu trapper)

Przykład:

```text
info from server: "processed: 1; failed: 0; total: 1; seconds spent: 0.000052"
sent: 1; skipped: 0; total: 1
```

🔤 **zabbix\_sender** = Zabbix sender: wysyła pojedynczą wartość do elementu typu trapper w Zabbixie

</div><div id="bkmrk-%F0%9F%9F%A2-tylko-odczyt-skryp" style="border:1px solid rgba(22,163,74,.35);border-left:6px solid #16a34a;border-radius:10px;padding:12px 18px 6px 18px;margin:20px 0;background:rgba(22,163,74,.06)"><span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#16a34a;color:#fff">🟢 TYLKO ODCZYT</span>

### Skrypt Pythona: w1\_do\_zabbixa.py

```python
#!/usr/bin/env python3
# -*- coding: utf-8 -*-
"""Odczyt czujników DS18B20 z magistrali 1-Wire i wysyłka do Zabbixa przez zabbix_sender."""
import os
import subprocess
import sys

SERWER_ZABBIXA = "mon01"
NAZWA_HOSTA = "czujnik-rpi01"
KATALOG_W1 = "/sys/bus/w1/devices"

# numer czujnika z katalogu 28-... -> klucz elementu typu trapper w Zabbixie
CZUJNIKI = {
    "28-3c01d6075a21": "temp.wlot.dol",
    "28-3c01d6075b32": "temp.wlot.srodek",
    "28-3c01d6075c43": "temp.wlot.gora",
}


def odczytaj(numer, katalog=KATALOG_W1):
    """Zwraca temperaturę w °C albo None, gdy odczyt jest niepewny."""
    sciezka = os.path.join(katalog, numer, "w1_slave")
    try:
        with open(sciezka, encoding="ascii") as plik:
            linie = plik.read().splitlines()
    except OSError as blad:
        print("Brak odczytu %s: %s" % (numer, blad), file=sys.stderr)
        return None
    if len(linie) < 2 or not linie[0].endswith("YES"):
        print("Błędna suma kontrolna: %s" % numer, file=sys.stderr)
        return None
    pozycja = linie[1].find("t=")
    if pozycja < 0:
        return None
    mc = int(linie[1][pozycja + 2:])
    if mc == 85000:
        # 85,0 °C to wartość startowa układu, nie pomiar
        print("Wartość startowa 85 °C: %s" % numer, file=sys.stderr)
        return None
    return mc / 1000.0


def wyslij(wartosci):
    """Wysyła pary (klucz, wartość) jednym wywołaniem zabbix_sender."""
    wejscie = "".join(
        "%s %s %.3f\n" % (NAZWA_HOSTA, klucz, temp) for klucz, temp in wartosci
    )
    wynik = subprocess.run(
        ["zabbix_sender", "-z", SERWER_ZABBIXA, "-i", "-"],
        input=wejscie, text=True, capture_output=True, timeout=30,
    )
    print(wynik.stdout.strip())
    return wynik.returncode


def main():
    wartosci = []
    for numer, klucz in CZUJNIKI.items():
        temp = odczytaj(numer)
        if temp is not None:
            wartosci.append((klucz, temp))
    if not wartosci:
        print("Żaden czujnik nie dał poprawnego odczytu", file=sys.stderr)
        return 1
    return wyslij(wartosci)


if __name__ == "__main__":
    sys.exit(main())
```

Skrypt czyta pliki `w1_slave`, odrzuca odczyty z błędną sumą kontrolną i wartość startową 85 °C, a resztę wysyła jednym wywołaniem `zabbix_sender` na standardowe wejście programu. Numery w słowniku `CZUJNIKI` podmieniamy na numery z fiszki z listą czujników. Skrypt kompiluje się poleceniem `python3 -m py_compile`.

🔤 **DS18B20** = Cyfrowy czujnik temperatury z magistralą 1-Wire, z fabrycznym 64-bitowym adresem, popularny w układach domowych i małych serwerowniach

</div><div id="bkmrk-%F0%9F%9F%A0-zmienia-system-ins-2" style="border:1px solid rgba(217,119,6,.35);border-left:6px solid #d97706;border-radius:10px;padding:12px 18px 6px 18px;margin:20px 0;background:rgba(217,119,6,.06)"><span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#d97706;color:#fff">🟠 ZMIENIA SYSTEM</span>

### Instalacja skryptu: sudo install

```bash
sudo install -m 0755 w1_do_zabbixa.py /usr/local/bin/w1_do_zabbixa.py
```

🔤 **install** = install: kopiuje pliki i tworzy katalogi z jednoczesnym ustawieniem uprawnień

</div><div id="bkmrk-%F0%9F%9F%A2-tylko-odczyt-uruch" style="border:1px solid rgba(22,163,74,.35);border-left:6px solid #16a34a;border-radius:10px;padding:12px 18px 6px 18px;margin:20px 0;background:rgba(22,163,74,.06)"><span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#16a34a;color:#fff">🟢 TYLKO ODCZYT</span>

### Uruchomienie skryptu: python3 w1\_do\_zabbixa.py

```bash
python3 /usr/local/bin/w1_do_zabbixa.py
```

Przykład:

```text
info from server: "processed: 3; failed: 0; total: 3; seconds spent: 0.000081"
sent: 3; skipped: 0; total: 3
```

🔤 **python3** = uruchom interpreter Pythona w wersji 3 albo wskazany skrypt

</div><div id="bkmrk-%F0%9F%9F%A0-zmienia-system-zad" style="border:1px solid rgba(217,119,6,.35);border-left:6px solid #d97706;border-radius:10px;padding:12px 18px 6px 18px;margin:20px 0;background:rgba(217,119,6,.06)"><span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#d97706;color:#fff">🟠 ZMIENIA SYSTEM</span>

### Zadanie cykliczne: /etc/cron.d/w1-zabbix

```text
* * * * * nazwa_usera /usr/bin/python3 /usr/local/bin/w1_do_zabbixa.py 2>&1 | logger -t w1-zabbix
```

Wpis w katalogu `/etc/cron.d/` uruchamia skrypt co minutę jako wskazany użytkownik, a wynik trafia do dziennika systemowego pod znacznikiem `w1-zabbix`.

</div>## Z życia wzięte

<div id="bkmrk-%F0%9F%93%96-z-%C5%BBycia-wzi%C4%98teponi" style="border-left:6px solid #b45309;border-radius:10px;padding:14px 18px;margin:18px 0;background:rgba(180,83,9,.07)"><span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#b45309;color:#fff">📖 Z ŻYCIA WZIĘTE</span>

Poniedziałek, 7:35. Tomek wchodzi do serwerowni w Pamiątkowie i czuje, że jest ciepło, a wyświetlacz klimatyzatora pokazuje błąd po sobotnim zaniku zasilania. W Zabbixie nie ma żadnego alarmu, bo `hv02` i `hv01` zgłaszały ostrzeżenia temperatury tylko w swoich własnych logach, których nikt nie czytał. Serwery przetrwały dzięki zapasowi w ustawieniach wentylatorów, ale zespół uznał, że o przegrzaniu ma dowiadywać się z alarmu, a nie z zapachu. Tego samego dnia Tomek zamawia cztery sondy i płytkę, a do wieczora z Olą opisują, gdzie je zamontują.

</div>## Projekt DIY krok po kroku

Zestaw mierzy temperaturę w czterech miejscach: trzy sondy na wlocie szafy (dół, środek, góra) i jedna w gorącym korytarzu. Dlaczego akurat tam, wyjaśnia strona [Termometry: rodzaje, zasada działania i zastosowania](https://wiedza.konio-dc.eu/books/warstwa-fizyczna/page/termometry-rodzaje-zasada-dzialania-i-zastosowania). Pierwsze trzy punkty to wartości, na których opiera się alarm, a czwarty służy do trendów i oceny różnicy temperatur.

### Lista części

<table id="bkmrk-cz%C4%99%C5%9B%C4%87po-couwagip%C5%82ytk"><thead><tr><th>Część</th><th>Po co</th><th>Uwagi</th></tr></thead><tbody><tr><td>Płytka ESP32 DevKit z modułem ESP32</td><td>procesor z Wi-Fi, który odczytuje czujniki i udostępnia je w sieci</td><td>płytka z gniazdem USB i wyprowadzonym pinem 3V3</td></tr><tr><td>Cztery sondy DS18B20 w stalowej gilzie na kablu</td><td>czujniki temperatury</td><td>wodoodporne sondy mają trzy przewody, a ich kolory różnią się między producentami</td></tr><tr><td>Rezystor 4,7 kΩ</td><td>podciągnięcie linii danych do 3,3 V</td><td>jeden na całą magistralę</td></tr><tr><td>Kabel trzyżyłowy albo skrętka</td><td>przedłużenie sond do miejsc w szafie</td><td>trzy żyły: zasilanie, masa i dane</td></tr><tr><td>Listwa zaciskowa albo lutowane połączenia z koszulkami</td><td>równoległe połączenie sond</td><td>sprawdzone, pewne styki</td></tr><tr><td>Zasilacz USB 5 V z certyfikatem CE</td><td>zasilanie płytki</td><td>z listwy w szafie, najlepiej z gniazda objętego zasilaniem awaryjnym</td></tr><tr><td>Obudowa na płytkę</td><td>ochrona przed kurzem i przypadkowym zwarciem</td><td>otwory na kable i dostęp do portu USB</td></tr><tr><td>Opaski, uchwyty i taśma dwustronna</td><td>mocowanie sond</td><td>z tworzywa, żeby sonda nie dotykała metalowej szafy</td></tr><tr><td>Termometr wzorcowy z certyfikatem wzorcowania</td><td>sprawdzenie sond</td><td>albo zlecenie wzorcowania w laboratorium</td></tr><tr><td>Lód i woda</td><td>punkt odniesienia 0 °C</td><td>w naczyniu o wysokich ściankach</td></tr></tbody></table>

### Schemat połączeń

[![Rysunek 6. Schemat połączeń: wszystkie sondy podłączamy równolegle do zasilania 3,3 V, masy i jednej linii danych na pinie GPIO4. Jeden rezystor 4,7 kΩ między 3,3 V a linią danych obsługuje całą magistralę](https://wiedza.konio-dc.eu/uploads/images/gallery/2026-10/fiz-termometry-esp32-ds18b20.png)](https://wiedza.konio-dc.eu/uploads/images/gallery/2026-10/fiz-termometry-esp32-ds18b20.png)

*🔎 Rysunek 6. Schemat połączeń: wszystkie sondy podłączamy równolegle do zasilania 3,3 V, masy i jednej linii danych na pinie GPIO4. Jeden rezystor 4,7 kΩ między 3,3 V a linią danych obsługuje całą magistralę (kliknięcie otwiera pełny rozmiar)*

Wszystkie cztery sondy łączymy równolegle, bo każda ma własny 64-bitowy adres i magistrala 1-Wire rozróżnia je po nim \[9\]. Zasilamy je z pinu 3V3 płytki, a rezystor 4,7 kΩ łączymy między 3V3 i linią danych. Dokumentacja ESPHome dopuszcza wartości w granicach ±1 kΩ, o ile kable nie są niezwykle długie \[3\].

[![Czujnik DS18B20 od SparkFun. Takie sondy łączymy równolegle do jednej linii danych, a kolory przewodów sprawdzamy w opisie konkretnej sondy.](https://commons.wikimedia.org/wiki/Special:FilePath/SparkFun_DS18B20_2.jpg?width=960)](https://commons.wikimedia.org/wiki/File:SparkFun_DS18B20_2.jpg)

*📷 Czujnik DS18B20 od SparkFun. Takie sondy łączymy równolegle do jednej linii danych, a kolory przewodów sprawdzamy w opisie konkretnej sondy. Źródło: [Wikimedia Commons](https://commons.wikimedia.org/wiki/File:SparkFun_DS18B20_2.jpg) (autor i wolna licencja podane na stronie pliku).*

Układ DS18B20 można też zasilać z linii danych (zasilanie pasożytnicze), ale w serwerowni wybieramy osobny przewód zasilający, bo daje stabilniejsze odczyty na dłuższym kablu \[9\]. Odwrotnie podłączone zasilanie nagrzewa i niszczy układ, więc kolory przewodów sprawdzamy w opisie sondy.

### Pierwsze uruchomienie i adresy czujników

Najpierw wgrywamy plik tylko z sekcjami `wifi`, `api`, `ota` i `one_wire`, bez sekcji `sensor`. Po starcie dziennik (fiszka Odczyt adresów czujników) pokazuje cztery adresy, bo skanowanie magistrali działa także bez opisanych czujników \[3\].

Żeby poznać, który adres należy do której sondy, ogrzewamy ją w dłoni i obserwujemy, która wartość rośnie. Potem uzupełniamy plik o sekcję `sensor` z właściwymi adresami i nazwami `wlot_dol`, `wlot_srodek`, `wlot_gora` i `korytarz_goracy`. Adresów nie zastępujemy numerami kolejnymi (`index`), bo kolejność zmienia się po dodaniu albo wymianie sondy \[4\].

### Montaż w szafie

Trzy sondy mocujemy na wlocie najwyższego, środkowego i najniższego serwera, około 5 cm przed obudową, tak jak opisuje <abbr title="American Society of Heating, Refrigerating and Air-Conditioning Engineers: amerykańskie stowarzyszenie inżynierów, którego zalecenia opisują temperaturę i wilgotność w serwerowniach">ASHRAE</abbr> przy sprawdzaniu instalacji \[11\]. Czwartą sondę zawieszamy za szafą, w gorącym korytarzu, mniej więcej na środku wysokości. Kable prowadzimy wzdłuż prowadnic szafy, a nie przez wlot powietrza, i nie zasłaniamy wentylatorów.

<div id="bkmrk-%F0%9F%93%B8-zrzut-ekranu-do-uz" style="border:2px dashed rgba(100,116,139,.6);border-radius:10px;padding:14px 18px;margin:18px 0;background:rgba(100,116,139,.06)"><span style="display:inline-block;padding:2px 10px;margin:0 6px 4px 0;border-radius:999px;font-size:12px;font-weight:700;letter-spacing:.02em;background:#64748b;color:#fff">📸 ZRZUT EKRANU DO UZUPEŁNIENIA</span>

Zdjęcie do zrobienia po montażu: szafa 1 z frontu, trzy sondy na wlocie na trzech wysokościach i opis każdej sondy na kablu.

</div>Płytkę ESP32 montujemy poza strumieniem gorącego powietrza, najlepiej z boku szafy od strony zimnego korytarza. Sondy opisujemy na obu końcach kabla, a adresy zapisujemy w tabeli w NetBoxie przy szafie.

### Kalibracja i porównanie z wzorcem

<div class="callout info" id="bkmrk-poj%C4%99cie%3A-wzorcowanie">**Pojęcie: wzorcowanie.** Porównanie wskazań przyrządu z wzorcem o znanej, wyższej dokładności i zapisanie różnicy. Oddzielnym krokiem jest regulacja, czyli poprawienie wskazań, na przykład przez dopisanie stałej poprawki w pliku konfiguracyjnym.

</div>Punkt 0 °C przygotowujemy w kąpieli lodowej. Wysokie naczynie napełniamy po brzegi pokruszonym lodem, dolewamy wody tak, żeby sięgała pół centymetra poniżej brzegu, i czekamy minutę lub dwie \[12\]. Sondy zanurzamy w środku mieszaniny i delikatnie mieszamy, żeby nie dotykały ścianek ani dna, bo wtedy wynik jest fałszywy \[12\].

Dobrze przygotowana kąpiel ma 0 °C z dokładnością do ułamków stopnia, a źle przygotowana, na przykład zwykła szklanka z kostkami lodu, potrafi pokazać kilkanaście stopni za dużo \[12\]. DS18B20 w tym zakresie ma gwarantowane ±0,5 °C \[9\]. Odczyt zapisujemy dla każdej sondy osobno.

Drugi punkt wybieramy blisko temperatury pracy, w pokoju około 22 do 25 °C. Wszystkie sondy leżą obok siebie z wzorcowym termometrem w tym samym miejscu przez co najmniej kilkanaście minut, a potem porównujemy odczyty. Różnice poniżej ±0,5 °C przyjmujemy bez zmian, a większe korygujemy poprawką `offset` w sekcji `filters` danej sondy.

### Obudowa i miejsce montażu

Obudowa płytki ma dostęp powietrza, bo ESP32 się grzeje i nie powinien podgrzewać sond. Sondy wychodzą kablem na zewnątrz i nie wiszą przy samej obudowie płytki. Płytkę zasilamy zasilaczem USB z listwy w szafie, a kabel USB prowadzimy tak, żeby nikt nie zahaczył o niego przy pracach w szafie.

## Drugi wariant: Raspberry Pi

Ten sam czujnik DS18B20 podłączamy do Raspberry Pi. Fizycznie łączymy pin 1 (3,3 V), pin 7 (GPIO4) i pin 9 (masa) z trzema żyłami sond, a rezystor 4,7 kΩ stawiamy między pinami 1 i 7. Schemat jest ten sam co na Rysunku 6, tylko zamiast płytki ESP32 stoi złącze malinki.

Włączamy nakładkę 1-Wire fiszkami Edycja pliku konfiguracyjnego, Włączenie magistrali i Ponowne uruchomienie. Nakładka `w1-gpio` ma też wariant `w1-gpio-pi5`, opisany jako wersja dla Raspberry Pi 5 \[8\]. Po restarcie czujniki widać w katalogu `/sys/bus/w1/devices/`.

Dane trafiają do Zabbixa przez element typu trapper, a nie przez odpytywanie. Skrypt z fiszki Skrypt Pythona czyta czujniki i co minutę wysyła wartości do `mon01` programem `zabbix_sender` \[10\]. Host w Zabbixie nazywa się tak samo jak `NAZWA_HOSTA` w skrypcie, czyli `czujnik-rpi01`.

## Integracja z monitoringiem

[![Rysunek 7. Droga danych do Zabbixa: Zabbix sam pyta płytkę ESP32 przez HTTP, a malinka wysyła wartości przez zabbix_sender. Oba źródła spotykają się w wyzwalaczach na mon01](https://wiedza.konio-dc.eu/uploads/images/gallery/2026-10/fiz-termometry-droga-zabbix.png)](https://wiedza.konio-dc.eu/uploads/images/gallery/2026-10/fiz-termometry-droga-zabbix.png)

*🔎 Rysunek 7. Droga danych do Zabbixa: Zabbix sam pyta płytkę ESP32 przez HTTP, a malinka wysyła wartości przez zabbix\_sender. Oba źródła spotykają się w wyzwalaczach na mon01 (kliknięcie otwiera pełny rozmiar)*

Dla ESP32 wybieramy odpytywanie. Zabbix co minutę pyta płytkę o wartości przez serwer HTTP ESPHome, a odpowiedź JSON ma pole `value`, które element wyciąga ścieżką <abbr title="Zapis ścieżki, która wskazuje jedną wartość w dokumencie JSON, np. $.value to pole value na samym wierzchu">JSONPath</abbr> \[6\]. Dzięki temu na płytce nie trzeba żadnych dodatków, a gdy płytka milknie, Zabbix to widzi.

### Host i makra w Zabbixie

<div class="callout info" id="bkmrk-poj%C4%99cie%3A-element-htt">**Pojęcie: element HTTP agent.** Element danych, który sam wysyła zapytanie HTTP pod wskazany adres i przetwarza odpowiedź. Typ elementu opisuje strona o pojęciach Zabbixa, a w wersji 7.0 pozwala na uwierzytelnianie podstawowe i przetwarzanie wstępne JSONPath \[13\].

</div>Ścieżka w interfejsie, w której tworzymy host:

```text
Data collection → Hosts → Create host
```

Host nazywamy `esp02`, dodajemy go do nowej grupy `Czujniki środowiska` i nie dodajemy żadnego interfejsu agenta, bo na płytce nie działa agent Zabbixa. Na hoście ustawiamy makra z tabeli.

<table id="bkmrk-makrowarto%C5%9B%C4%87po-co%7B%24c"><thead><tr><th>Makro</th><th>Wartość</th><th>Po co</th></tr></thead><tbody><tr><td>`{$CZUJNIK.ADRES}`</td><td>`10.20.10.71`</td><td>adres płytki ESP32</td></tr><tr><td>`{$CZUJNIK.UZYTKOWNIK}`</td><td>nazwa użytkownika z sekcji `web_server`</td><td>uwierzytelnianie do serwera HTTP</td></tr><tr><td>`{$CZUJNIK.HASLO}`</td><td>hasło z sekcji `web_server`, typ Secret text</td><td>hasło nie jest widoczne w interfejsie</td></tr><tr><td>`{$TEMP.WLOT.OSTRZEZENIE}`</td><td>`27`</td><td>górna granica zalecana (°C)</td></tr><tr><td>`{$TEMP.WLOT.KRYTYCZNY}`</td><td>`32`</td><td>górna granica dopuszczalna klasy A1 (°C)</td></tr></tbody></table>

Progi wynikają z zaleceń ASHRAE: 27 °C to górna granica zalecanego zakresu wlotu 18 do 27 °C, a 32 °C to górna granica zakresu dopuszczalnego klasy A1 \[11\]\[14\]. Jeśli karta katalogowa serwera przewiduje klasę A2 albo szerszą, próg krytyczny podnosimy zgodnie z nią.

### Elementy danych

Dla każdej sondy tworzymy jeden element. Zasady są takie same, zmienia się tylko nazwa i końcówka adresu.

<table id="bkmrk-nazwatypkluczurlprze"><thead><tr><th>Nazwa</th><th>Typ</th><th>Klucz</th><th>URL</th><th>Przetwarzanie wstępne</th></tr></thead><tbody><tr><td>Wlot, dół</td><td>HTTP agent</td><td>`temp.wlot.dol`</td><td>`http://{$CZUJNIK.ADRES}/sensor/wlot_dol`</td><td>JSONPath `$.value`</td></tr><tr><td>Wlot, środek</td><td>HTTP agent</td><td>`temp.wlot.srodek`</td><td>`http://{$CZUJNIK.ADRES}/sensor/wlot_srodek`</td><td>JSONPath `$.value`</td></tr><tr><td>Wlot, góra</td><td>HTTP agent</td><td>`temp.wlot.gora`</td><td>`http://{$CZUJNIK.ADRES}/sensor/wlot_gora`</td><td>JSONPath `$.value`</td></tr><tr><td>Gorący korytarz</td><td>HTTP agent</td><td>`temp.korytarz.goracy`</td><td>`http://{$CZUJNIK.ADRES}/sensor/korytarz_goracy`</td><td>JSONPath `$.value`</td></tr></tbody></table>

W każdym elemencie ustawiamy: typ informacji liczba zmiennoprzecinkowa, jednostka `°C`, interwał 1m, uwierzytelnianie podstawowe z makrami użytkownika i hasła, a historię i trendy według zasad bazy. Wartość `NaN` z uszkodzonej sondy nie przejdzie przez konwersję na liczbę, więc element stanie się niewspierany, a wtedy zadziała alarm braku danych.

Dla wariantu z malinką tworzymy host `czujnik-rpi01` z trzema elementami typu Zabbix trapper o kluczach `temp.wlot.dol`, `temp.wlot.srodek` i `temp.wlot.gora`. W polu Allowed hosts wpisujemy adres Raspberry Pi. Wartości wysyła skrypt, a nazwa hosta w wywołaniu musi być identyczna z nazwą w Zabbixie \[10\].

### Wyzwalacze

Wyrażenia zapisujemy w składni Zabbixa 7.0, w której nazwę hosta i klucz podajemy w ukośnikach \[15\]. Próg ostrzegawczy sprawdzamy na wartości minimalnej z pięciu minut, czyli alarm zgłaszamy dopiero wtedy, gdy każdy odczyt w tym czasie jest powyżej progu.

Ostrzeżenie o wysokiej temperaturze na wlocie (poziom Warning):

```text
min(/esp02/temp.wlot.gora,5m)>{$TEMP.WLOT.OSTRZEZENIE}
or min(/esp02/temp.wlot.srodek,5m)>{$TEMP.WLOT.OSTRZEZENIE}
or min(/esp02/temp.wlot.dol,5m)>{$TEMP.WLOT.OSTRZEZENIE}
```

Wyrażenie powrotu, które daje histerezę jednego stopnia, żeby alarm nie migał na granicy:

```text
max(/esp02/temp.wlot.gora,5m)<{$TEMP.WLOT.OSTRZEZENIE}-1
and max(/esp02/temp.wlot.srodek,5m)<{$TEMP.WLOT.OSTRZEZENIE}-1
and max(/esp02/temp.wlot.dol,5m)<{$TEMP.WLOT.OSTRZEZENIE}-1
```

Alarm krytyczny, wyższy próg i krótszy czas (poziom Disaster):

```text
min(/esp02/temp.wlot.gora,3m)>{$TEMP.WLOT.KRYTYCZNY}
or min(/esp02/temp.wlot.srodek,3m)>{$TEMP.WLOT.KRYTYCZNY}
or min(/esp02/temp.wlot.dol,3m)>{$TEMP.WLOT.KRYTYCZNY}
```

Brak danych z któregokolwiek czujnika (poziom High):

```text
nodata(/esp02/temp.wlot.gora,5m)=1
or nodata(/esp02/temp.wlot.srodek,5m)=1
or nodata(/esp02/temp.wlot.dol,5m)=1
or nodata(/esp02/temp.korytarz.goracy,5m)=1
```

Funkcje `min`, `max` i `nodata` oraz wyrażenie powrotu to standardowe elementy składni wyzwalaczy Zabbixa \[15\]. Sondy w gorącym korytarzu nie obejmujemy alarmem temperatury, bo wylot jest z natury cieplejszy. Zbieramy z niej historię, żeby widzieć różnicę temperatur między korytarzami.

### Akcja: poczta i SMS

Ścieżka w interfejsie, w której tworzymy akcję:

```text
Alerts → Actions → Trigger actions → Create action
```

Dla poziomów od Warning w górę wysyłamy wiadomość pocztą do grupy użytkowników <abbr title="Information Technology: dział albo praca związana z komputerami i infrastrukturą firmy">IT</abbr>. Dla poziomu Disaster dodajemy drugą operację, czyli <abbr title="Short Message Service: krótka wiadomość tekstowa na telefon, która dociera także bez internetu">SMS</abbr> przez typ nośnika SMS z modemem albo przez webhook do bramki SMS. Zasady łączenia zdarzenia z reakcją opisuje strona o pojęciach Zabbixa.

Test progów robimy bez grzania szafy: tymczasowo obniżamy makra `{$TEMP.WLOT.OSTRZEZENIE}` i `{$TEMP.WLOT.KRYTYCZNY}` do kilku stopni powyżej bieżącej temperatury, a sondę ogrzewamy w dłoni. Po sprawdzeniu, że alarmy i wiadomości dochodzą, przywracamy 27 i 32.

## Bezpieczeństwo i ograniczenia

Własny czujnik nie ma świadectwa wzorcowania ani deklaracji zgodności, a jego dokładność wynika wyłącznie z karty katalogowej DS18B20 i z naszej kalibracji w kąpieli lodowej. Dlatego traktujemy go jako uzupełnienie istniejącego monitoringu, a nie jego zastąpienie.

- Gwarancja i ubezpieczenie: urządzenie własnej roboty w szafie z serwerami może być sprzeczne z warunkami gwarancji sprzętu albo polisy. Przed montażem uzgadniamy je z zarządcą serwerowni i ubezpieczycielem, a prace wykonujemy tylko na niskim napięciu i z gotowym zasilaczem z oznaczeniem <abbr title="Community Edition: darmowa, społecznościowa wersja Dockera, w odróżnieniu od płatnej wersji Enterprise">CE</abbr>.
- Chłodnia w Swarzędzu: dla żywności głęboko mrożonej wymagane są rejestratory zgodne z EN 12830, EN 13485 i EN 13486, a zapisy przechowujemy co najmniej rok, więc zestaw <abbr title="Do It Yourself: zrób to sam, czyli własnoręcznie zbudowany czujnik zamiast gotowego urządzenia">DIY</abbr> ich nie zastępuje \[16\]\[17\].
- Sygnalizacja pożarowa: czujki temperatury w systemie <abbr title="Przeciwpożarowy: dotyczący ochrony przed pożarem, na przykład centrala ppoż.">ppoż.</abbr> podlegają serii norm EN 54 i odbiorowi, a nasz zestaw w żaden sposób ich nie zastępuje \[18\].
- Czujnik przy wylocie zasilacza serwera pokazuje temperaturę wylotu, nie wlotu. Montujemy sondy tylko na froncie szafy.
- Samonagrzewanie: sam DS18B20 grzeje się pomijalnie, ale płytka ESP32 i zasilacz USB nie, więc sondy prowadzimy kablem z dala od nich.
- Sieć: serwer HTTP ESPHome domyślnie używa uwierzytelniania podstawowego, a dokumentacja zapowiada zmianę domyślnego schematu na digest w wersji 2027.1.0 \[6\]. Na `fw01` ograniczamy dostęp do portu 80 płytki do adresu `mon01` i nie wystawiamy go poza serwery.
- Wi-Fi w serwerowni bywa niestabilne za metalowymi szafami. Jeśli odczyty wypadają, przechodzimy na wersję z przewodową siecią Ethernet, którą ESPHome również obsługuje.
- Aktualizacje: płytkę aktualizujemy przez sieć według sekcji `ota`, a przed aktualizacją sprawdzamy, że nie wypada okno zmian w listopadzie i styczniu.

## Częste błędy

<table id="bkmrk-objawprzyczynaco-rob"><thead><tr><th>Objaw</th><th>Przyczyna</th><th>Co robimy</th></tr></thead><tbody><tr><td>W dzienniku `Found no devices!`</td><td>brak rezystora podciągającego, zły pin albo odwrócone zasilanie</td><td>sprawdzamy 4,7 kΩ między 3V3 i linią danych, pin GPIO4 i kolory przewodów \[3\]</td></tr><tr><td>Sonda mocno się nagrzewa, a odczytu brak</td><td>odwrócone zasilanie</td><td>odłączamy zasilanie i wymieniamy sondę</td></tr><tr><td>Odczyt zawsze 85,0 °C</td><td>wartość startowa układu albo spadek napięcia</td><td>sprawdzamy zasilanie, dodajemy odrzucanie 85,0, jak w skrypcie \[9\]</td></tr><tr><td>Odczyty skaczą albo część brakuje</td><td>zbyt długi kabel, słabe styki</td><td>skracamy kabel, lutujemy zamiast skręcać, sprawdzamy rezystor \[3\]</td></tr><tr><td>Płytka restartuje się co 15 minut</td><td>sekcja `api` bez klienta i bez `reboot_timeout: 0s`</td><td>dopisujemy `reboot_timeout: 0s` albo przechodzimy na MQTT \[5\]</td></tr><tr><td>Element w Zabbixie niewspierany</td><td>błędny URL, hasło albo brak JSONPath</td><td>sprawdzamy `curl` z tego samego adresu i przetwarzanie wstępne `$.value`</td></tr><tr><td>`zabbix_sender` zgłasza `failed: 1`</td><td>nazwa hosta inna niż w Zabbixie, brak elementu trapper albo zły Allowed hosts</td><td>porównujemy nazwę hosta, klucz i adres nadawcy \[10\]</td></tr><tr><td>Odczyt w kąpieli lodowej 1 do 2 °C zamiast 0</td><td>lód bez wody, sonda przy ściance albo dnie</td><td>robimy kąpiel od nowa: pokruszony lód, woda, mieszanie, sonda w środku \[12\]</td></tr><tr><td>Czujnik w szafie pokazuje o kilka stopni za dużo</td><td>sonda przy wylocie zasilacza albo dotyka metalu</td><td>przenosimy na front i mocujemy w uchwycie z tworzywa</td></tr></tbody></table>

## 🎯 Ćwiczenia

1. Ile rezystorów 4,7 kΩ potrzeba przy czterech sondach DS18B20 na jednej magistrali?

<details id="bkmrk-odpowied%C5%BA-jeden%2C-na-"><summary>Odpowiedź</summary>

Jeden, na całą magistralę. Łączymy go między zasilaniem 3,3 V a linią danych, przy płytce \[3\].

</details>1. Dlaczego sondy zasilamy z pinu 3V3, a nie z 5 V?

<details id="bkmrk-odpowied%C5%BA-piny-gpio-"><summary>Odpowiedź</summary>

Piny <abbr title="General Purpose Input Output: uniwersalny pin mikrokontrolera, który można ustawić jako wejście albo wyjście">GPIO</abbr> płytki ESP32 pracują na 3,3 V, a linia danych jest podciągana do napięcia zasilania sond. DS18B20 wystarcza zasilanie od 3,0 do 5,5 V, więc 3,3 V jest bezpieczne dla obu stron \[9\].

</details>1. Jakie wyrażenie wyzwalacza zgłosi brak danych z sondy `temp.wlot.gora` po pięciu minutach?

<details id="bkmrk-odpowied%C5%BA-nodata%28%2Fes"><summary>Odpowiedź</summary>

`nodata(/esp02/temp.wlot.gora,5m)=1`. Wyzwalacz przejdzie w stan problemu, gdy przez pięć minut nie przyjdzie żadna wartość, także wtedy, gdy element stał się niewspierany \[15\].

</details>1. Sonda w kąpieli lodowej pokazuje 0,4 °C. Wymieniamy ją czy korygujemy?

<details id="bkmrk-odpowied%C5%BA-nie-wymien"><summary>Odpowiedź</summary>

Nie wymieniamy. Producent gwarantuje ±0,5 °C w tym zakresie, więc 0,4 °C mieści się w tolerancji \[9\]. Jeśli chcemy większej zgodności, dopisujemy poprawkę `offset: -0.4` w sekcji `filters` tej sondy, ale tylko po sprawdzeniu drugiego punktu z termometrem wzorcowym.

</details>1. Dlaczego czwarta sonda w gorącym korytarzu nie ma własnego alarmu temperatury?

<details id="bkmrk-odpowied%C5%BA-gor%C4%85cy-kor"><summary>Odpowiedź</summary>

Gorący korytarz jest z natury cieplejszy, bo zbiera powietrze po przejściu przez serwery. Zalecenia ASHRAE dotyczą wlotu, więc alarmy ustawiamy na trzech sondach przy froncie, a czwartą zbieramy tylko do historii i trendów \[11\]\[14\].

</details>**Źródła:**

1. [PyPI, esphome (wersja 2026.9.1, wymagany Python od 3.12)](https://pypi.org/project/esphome/)
2. [ESPHome, Native API Component](https://esphome.io/components/api/)
3. [ESPHome, 1-Wire Bus](https://esphome.io/components/one_wire/) oraz [1-Wire przez GPIO](https://esphome.io/components/one_wire/gpio/)
4. [ESPHome, Dallas Temperature Sensor](https://esphome.io/components/sensor/dallas_temp/)
5. [ESPHome, MQTT Client Component](https://esphome.io/components/mqtt/)
6. [ESPHome, Web Server Component](https://esphome.io/components/web_server/) oraz [Web Server API](https://esphome.io/web-api/)
7. [Raspberry Pi, config.txt](https://www.raspberrypi.com/documentation/computers/config_txt.html)
8. [Raspberry Pi, opis nakładek (overlays README)](https://github.com/raspberrypi/linux/blob/rpi-6.6.y/arch/arm/boot/dts/overlays/README)
9. [Analog Devices, karta katalogowa DS18B20](https://www.analog.com/media/en/technical-documentation/data-sheets/DS18B20.pdf)
10. [Zabbix 7.0, zabbix\_sender](https://www.zabbix.com/documentation/7.0/en/manual/concepts/sender) oraz [strona podręcznika zabbix\_sender](https://man.archlinux.org/man/zabbix_sender.1.en)
11. [Upsite, Data Center Temperature Sensor Location](https://www.upsite.com/blog/data-center-temperature-sensor-location/)
12. [ThermoWorks, How to Create a Properly Made Ice Bath](https://blog.thermoworks.com/thermal-secrets-creating-properly-made-ice-bath/)
13. [Zabbix 7.0, element HTTP agent](https://www.zabbix.com/documentation/7.0/en/manual/config/items/itemtypes/http)
14. [ASHRAE, Thermal Guidelines, 5th edition, karta referencyjna](https://www.ashrae.org/file%20library/technical%20resources/bookstore/supplemental%20files/therm-gdlns-5th-r-e-refcard.pdf)
15. [Zabbix 7.0, wyrażenia wyzwalaczy](https://www.zabbix.com/documentation/7.0/en/manual/config/triggers/expression)
16. [Rozporządzenie Komisji (WE) nr 37/2005](https://www.legislation.gov.uk/eur/2005/37/data.html)
17. [EVS, EN 12830:2018](https://www.evs.ee/en/evs-en-12830-2018)
18. [Wikipedia, EN 54](https://en.wikipedia.org/wiki/EN_54)